200NANO3CK**
E N G L I S H
DESCRIPTION
The Expert nano model 200NANO3CK is an electronic regulator
operating with microprocessor designed to control refrigerated
counters, display windows and static or ventilated refrigeration
units with off-cycle or electrical defrosting also in real time clock
(RTC). It is fitted with two analogue inputs for NTC temperature
probes, one digital input, three relays for the control of the
compressor, fans and defrosting function (the defrosting relay
can be configured as the light command) and buzzer. The
regulator can be also configured for heat applications.
PRINCIPAL CHARACTERISTICS
Can be configured for hot or cold applications.
Relay for controlling the compressor, evaporator fans and
defrosting elements (defrost output can be configured like light
output).
Clock for programmed defrosts (RTC)
Defrosting can be configured for off-cycle, heating element or cycle
inversion and frequency and duration can be set. End-of- defrosting
can be based on time or temperature.
Key operated manual START/STOP defrosting.
Key operated ON/OFF.
Cold room light ON/OFF switch with key or by means of door
switch (if defrost output is configured like cold room light).
Display/adjustment of temperature with decimal point.
Flat front surface for easy cleaning and keys of ample dimensions
which can be customised with various colours (on request).
3-Digit LED display with sign, decimal point and system status icon.
Internal buzzer for acoustic signals.
PEGO programming philosophy guaranteeing immediate start-up.
RS485 serial connection with Modbus-RTU or Telenet protocol.
IP65 front protection. Two-fold fastening option: clips / screws.
Voltage and terminal type depending on model.
HACCP function for memorization and visualization of the last
temperature alarm
NANO3CK SERIES MODELS
EXPERT NANO DESCRIPTION
PEGO CODE
Power 230Vac, 3 relays (8A+8A+16A), digital input,
200NANO3CK01
cold/hot function , RTC, RS485, Buzzer, fixed clamps.
Power 12Vac/ac, 3 relays (8A+8A+16A), digital input,
200NANO3CK11
hot/cold function, RTC, RS485, Buzzer, fixed clamps.
TECHNICAL DATA
Power voltage
Model 200NANO3CK01
230 V~ +10/-15% 50/60Hz
Model 200NANO3CK11
12V~ +10/-15% 50/60Hz / 12Vdc +10/-15% class 2
Absorbed power
3 VA Max
Environment conditions
Operating temperature
-5T55°C - humidity < 90% Rel. Hum. Not condensing
Storage temperature
-20T70°C - humidity < 90% Rel. Hum. Not condensing
Environments with strong vibrations or impacts; aggressive, polluted
Unsuitable operating
or corrosive atmospheres, exposure to direct solar radiation,
environments
explosive atmospheres or flammable gas.
General characteristics
Display
3-Digit with sign, decimal point and 9 LED status indicators
Resolution
0.1 °C
Probe precision (electronic)
± 0.5 °C
Reading range
-45T99 °C
Power clamps: fixed, screw for cables with c/section 0.2 to 2.5mm
Model 200NANO3CK01
Model 200NANO3CK11
Signal clamps: fixed, screw for cables with c/section 0.2 to 1.5mm
Model 200NANO3CK01
Clock for programmed defrosts (RTC)
Model 200NANO3CK11
Software class: A / Parameters saved on non-volatile memory (EEPROM)
Input characteristics
Analogue inputs
2 Inputs for NTC probes (10K Ώ 1% at 25°C)
Digital inputs
1 Input (clean contact)
Output characteristics
Compressor relay (DO1)
N.O. 16(6)A / 250V~
Heating elements relay
N.O. 8(3)A N.C. 6(3)A / 250V~
(DO2)
Fan relay (DO3)
N.O. 8(3)A / 250V~
Buzzer
Present
Dimensional, insulation and mechanical characteristics
93x37x65mm Depth 59mm
Dimensions
(Depth 69mm with removable clamps)
Drill hole template
71x29mm (+0.2/-0.1mm)
Front protection rating
IP65 with front board installation
In front of board by means of rear fastening clips or or two front
Installation
screws
Plastic PC+ABS UL94 V-0 body, PC transparent front, Key panel PC
Casing
or PC+ABS
Insulation type
Class II
Conformity with EU low voltage directives, electromagnetic compatibility and EC mark
Conforms to following EU Directives: Directives 2014/30/EU, 2014/35/EU.
Conforms to following harmonised standards:
EN60730-1:2016, EN60730-2-9:2010, EN61000-6-1:2007, EN61000-6-3:2007
Manuel d'utilisation et de maintenance / Use and maintenance manual
200NANO3CK01_01-18_FRA_ENG # Rev.01-18 # 22/02/2018
Régulateur de température électronique / Electronic thermostat
KEY FUNCTIONS
Key
UP KEY
Increases values / Scrolls parameters in ascending
order / Deactivates acoustic alarm if present /
Acknowledges an alarm. With variable dO2=1 if
pressed for over 3 sec, activates/deactivates room
light (DO2 output). With manual activation/
deactivation of the light a BIP is generated to confirm.
DOWN KEY
Decreases values / Scrolls parameters in descending
order / If pressed for over 3 sec. activates manual
defrosting (if suitable conditions are present).
Terminates defrosting if pressed for over 3 sec. during
the defrosting process. With manual activation/
deactivation of defrosting a BIP is generated to
confirm.
STAND-BY KEY
If pressed for over 1 sec. alternates the Stand-By with
Stand
normal mode and vice versa. When mode is
alternated a BIP is generated to confirm. In Stand-By
by
mode the system stops and the display signals OFF
and the temperature alternating.
SET KEY
Displays the set point.
Allows the set point to be entered when pressed in
combination with the DOWN or UP keys. Resets the
acoustic alarm if present.
STATUS ICON
ICON
COLD FUNCTION ICON (icon activated with mOd=0)
Led OFF = Cold function OFF
Led ON = Cold function ON
Flashing Led = Cold function ON waiting for C1 delay
HOT FUNCTION ICON (icon activated with mOd=1)
Led OFF = Hot function OFF
Led ON = Hot function ON
FAN ICON
Led OFF = Fans OFF
Led ON = Fans ON
Flashing Led = Fans paused after defrosting (see
parameter F5)
DEFROSTING ICON (icon activated with mOd=0)
Led OFF = Defrosting OFF
Led ON = Defrosting ON
Led Flashing = Dripping in progress after defrosting
(see parameter d7)
DOOR SWITCH / ROOM LIGHT ICON
Led OFF = Door switch not activated or not used and
room light off
Led ON = Room light ON (function active only if
variable dO2=1)
Flashing Led = Door switch activated or room light ON
with alarm E8.
ALARM ICON
Led OFF = No alarm present
Led ON = Indicates temperature alarm intervention
with remedy (HACCP alarm).
Flashing Led = Alarm present
2
2
FUNCTION
MEANING
DIMENSIONS (mm)
Optional
Optional
DRILL HOLE TEMPLATE (mm)
Expert nano LINE
COMBINED ACTIVATION OF KEYS AND THEIR FUNCTIONS
FUNCTION / KEY COMBINATION
(Set + o )
SETTINGS PROGRAMMING /
Press the SET key to view the current SETPOINT value
(temperature).
Keeping the SET key down and pressing either the () or ()
key, the SETPOINT value can be changed.
Release the SET key to return to view the room temperature;
the changes made will be automatically saved.
( + )
LEVEL 1 PROGRAMMING /
Press the UP and DOWN keys simultaneously for over 3 sec. to
access the Level 1 programming menu. When the menu is
accessed, a BIP is generated to confirm. The system leaves the
menu after 30 seconds.
/ (++Stand-by)
LEVEL 2 PROGRAMMING
Press the UP, DOWN and STAND-BY keys simultaneously for
over 3 sec. to access the Level 1 programming menu. When the
menu is accessed, a BIP is generated to confirm and the system
is placed in Stand-By mode.
HACCP MENU FOR VISUALIZATION OF THE LAST
TEMPERATURE ALARM RECORDING /
Push UP and STAND-BY keys simultaneously for over 3 seconds
to access the HACCP menu.
A BIP is generated to confirm.
( + )
EXIT PROGRAMMING MENUS /
Pressing the UP and DOWN buttons simultaneously in any
programming menu for over 3 sec. causes the system to save
the settings entered and leave that menu. A BIP is generated to
confirm.
ELECTRICAL CONNECTIONS
SUPPLY
(depending on model)
FASTENING TO PANEL BY MEANS OF TWO BACK CLIPS
K
Push to
remove
FASTENING TO PANEL BY MEANS OF TWO FRONT SCREW
Screw2.9x9.5m
m
PEGO S.r.l.
Via Piacentina, 6/b - 45030 - ROVIGO
Tel : +39(0)425 762906 - Fax: +39(0)425 762905
www.pego.it - e-mail: info@pego.it
(+ Stand-by)
Panel
2.9x9.5mm
screw
Distance between hole
centres : 77mm