7) Exit
» Press "set"
to return to the main menu.
5.8 Compensation with outside temperature.
T. Out.
Thanks to the outside temperature (via the WEB or connected to the boiler) the thermo-
stat calculates the boiler flow temperature, optimizing consumption. By acting on the pa-
rameter CLI (see installer menu PL), the contribution is adjusted according to the formula:
Tflow = Tclim + 10 x CLI x (T3-T4)
To disable the external probe, set CLI = 0, which gives:
Tflow = LLCH + 10 x (T3 - T4)
T3 = room set point
T4 = room temp
T clim = see chart
llCh = see installer menu PL