Register Nu-
Register Name
mber
201
Baud Rate
202
Parity
203
Stopbits
206
Delay Time
14.4 Mise en service
Register Nu-
Register Name
mber
3000
Byte Oder (Floating point
format)
3200
Distance unit
3201
Temperature unit
3401
Min.-Adjustment
3403
Max.-Adjustment
3600
Medium type
3601
Application liquid
3602
Application solid
VEGAPULS C 23 • Protocole Modbus et Levelmaster
Data type
Configurable Values
enum16
1200, 2400, 4800, 9600,
19200, 38400, 57600
r/w
enum8
0 = None, 1 = Odd, 2 =
Even
r/w
enum8
1 = None, 2 = Two
r/w
uint16
10 ... 250
r/w
Data type
Configurable Values
enum8
0=ABCD, 1=CDAB,
2=DCBA, 3=BADC
r/w
enum16
44=ft, 45=m, 47=in,
49=mm
r/w
enum16
32=°C, 33=°F, 35=K
r/w
float32
0 ... Measurement range
r/w
float32
0 ... Measurement range
r/w
enum16
0=Liquids, 1=Solids
r/w
enum16
0 =Storage tank, 1=
Storage tank (product agi-
r/w
tation), 2=Cargo tank,
3=Reactor tank, 4=Do-
sing tank, 5=Stilling pipe,
6=Bypass, 7=Outside of
plastic tank, 8=Outside
of mobile plastic tank,
9=Level of open water,
10=Open flume, 11=Water
weir, 12=Demonstration,
13=Pump station, 14=Col-
lection tank
enum16
0=Silo, 1= Bunker Big,
2=Bunker fast filling,
r/w
3=Profil registration heap,
4=Breaker mill, 5=De-
monstration
14 Annexe
Unit
Default Va-
lue
–
9600
–
0
–
1
ms
50
Unit
Default Va-
lue
–
0
-
m
-
°C
-
0
-
Measure-
ment range
-
Liquids
-
Storage
tank
-
Silo
53