Roomside / Flex
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO
PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer. If
you have questions, contact the manufacturer at the address or
telephone number listed in the warranty.
2. Before servicing or cleaning unit, switch power off at service panel
and lock the service disconnecting means to prevent power from
being switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
3. Installation work and electrical wiring must be done by a qualified
person(s) in accordance with all applicable codes and standards,
including fire-rated construction codes and standards.
4. Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to
prevent backdrafting. Follow the heating equipment manufacturer's
guideline and safety standards such as those published by the
National Fire Protection Association (NFPA), and the American
Society for Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
5. When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
6. Ducted fans must always be vented to the outdoors.
7. Acceptable for use over a tub or shower when connected to a GFCI
(Ground Fault Circuit Interrupter) - protected branch circuit (ceiling
installation only).
8. This unit must be grounded.
COOKING AREA
Do not install above or
inside this area.
o
45
NOT FOR USE IN
A COOKING AREA.
IMPORTANT - The ducting from this fan to the outside of the building
has a strong effect on the air flow, noise and energy use of the fan. Use
the shortest, straightest duct routing possible for best performance, and
avoid installing the fan with smaller ducts than recommended. Insulation
around the ducts can reduce energy loss and inhibit mold growth. Fans
installed with existing ducts may not achieve their rated airflow.
TM
Series Fan/Light
o
45
Cooking
Equipment
Floor
For Warranty Statement, Service Parts, Technical Support, or to
Register your product, please visit our website or call:
In the United States - Broan.com 800-637-1453 or NuTone.com
888-336-6151. In Canada - Broan.ca or NuTone.ca 877-896-1119
CAUTION
1. For general ventilating use only. Do not use to exhaust hazardous
or explosive materials and vapors.
2. This product can be installed in a wall if mounted 8-ft. or more
above the floor.
3. To avoid motor bearing damage and noisy and/or unbalanced
impellers, keep drywall spray, construction dust, etc. off power
unit.
4. Please read specification label on product for further information
and requirements.
CLEANING & MAINTENANCE
For quiet and efficient operation, long life, and attractive appearance
- lower or remove grille and vacuum interior of unit with the dusting
brush attachment.
The motor is permanently lubricated and never needs oiling. If the
motor bearings are making excessive or unusual noises, replace the
blower assembly (includes motor and impeller).
OPERATION
The fan and light can be operated separately. Use a 2-function wall
control.
Flex
TM
Series Fan/Light ONLY: Do not use a speed control to
operate the fan.
INSULATION
(Place around and
over fan housing.)
FAN
HOUSING
POWER
CABLE *
Seal gaps
around
housing.
4-IN. ROUND
DUCT*
Seal duct joints
with tape.
* Purchase separately.
OPTION - To mount housing anywhere between ceiling framing:
Use optional Hanger Bar Kit (sold separately from local distributors
or website). Follow mounting instructions included with kit.
1
ROOF CAP* (with built-in damper)
OR
WALL CAP*
(with built-in
4-IN. ROUND
damper)
ELBOWS*
Keep duct
runs short.