5.2
Mounting the product
Verify that the arrow at the discharge opening of the product (valve outlet)
matches the direction of flow of the liquid.
1. Mount the product in such a way that the liquid can escape via the dis-
charge opening without obstructions.
2. Mount the product in the cold water supply line to the drinking water
heater.
- A straight connection line with a maximum length of 1 m may be
installed between the product and the drinking water heater.
- The cross section of the connection line must correspond to the cross
section of the inlet of the product.
3. Tighten the connections with a maximum tightening torque of 18 Nm
when making the connections.
- Excessive tightening torque can cause cracks in the material which can
lead to leaks in the system.
5.3
Mounting the discharge line
HOT LIQUID
The liquid in systems is under high pressure and can have temperatures of up
to 95 °C.
•
Verify that the discharge line is installed in such a way that blown off liquid
cannot cause injury or damage.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
Verify that the discharge line is accessible and easy to oversee.
Verify that the drain line of the funnel has twice the cross section of the
inlet of the product.
1. The discharge line must have a gradient; its cross section must have at
least the same cross section as that of the discharge opening.
- The length of the discharge line must not exceed 2 m; the maximum
number of elbows is 2.
2. Route the end of the discharge line into an outlet or a container that can
hold the total capacity of the system.
Mounting
WARNING
EN
10
MSW