Télécharger Imprimer la page

Würth MULTI-TESTER PRO LED Traduction Des Instructions De Service D'origine page 10

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 19
Do not use with the battery compartment open!
The measuring lines must be disconnected from
the measuring circuit while the batteries are
changed.
A correct display is ensured within the tempera-
ture range of -10°C to 55°C.
The additionally displayed warning symbol and
acoustic signal at voltages > 35 V are intended
only as a warning of potentially fatal voltages,
not for measurement.
Proper use
DC voltage tests from 6 V to 1400 V, AC voltage
tests from 6 V to 1000 V, polarity, phase sequence
and continuity tests up to 50 kΩ and FI/RCD tests
can be carried out. Thanks to its high protection
class (IP65), Multi-Tester Pro-LED can be used even
under tough operating conditions.
Any other use is considered improper use.
The user is liable for damage resulting
from improper use.
10
Safety Instructions
Check the warning signal for audibility in loud
working environments before starting tests.
Replace the batteries immediately if a contin-
uous warning signal sounds when switching on.
In order to protect the device from being dam-
aged, remove the batteries if the device is not in
use for a prolonged period of time.
Use only genuine Würth accessories
and spare parts.
Item
Display
Nominal voltage
range
Input impedance
Indication
Frequency range
Switchable load
Cyclic duration factor
Continuity test
Protection category
Surge voltage cate-
gory
Test standard
Power supply
Technical data
0715 53 160
16 LEDs for voltage (12,
24, 48, 120, 230, 400,
690 and 1000 V),
polarity (+~-), continuity
(Rx/Ω) and phase/rotary
field (R/L) +PELV
3 ... 1000 V AC/DC
4 ... 1400 V AC/DC
285 kΩ
0.85 Un
0 ... 400 Hz
30 mA at 230 V
30 s ON/240 s OFF
0 ... 50 kΩ
IP 65
CAT IV 1000 V
IEC/EN 61243-3
2 x 1.5 V type AAA Micro
Item 0827 111

Publicité

loading

Ce manuel est également adapté pour:

0715 53 160