PROGRAMMING INSTRUCTIONS -
BASIC SETTINGS
Before entering the programming mode, make sure that
the appliance is in the service mode.
In case no button is pressed in a period of 5 min, the
control panel will automatically return to the service mode;
any changes made will NOT be saved!
1. Press the scroll
button and hold it for 2 sec until the
display shows:
Language:English
Press the up
or down
language.
2. Press the scroll
button again; the display will show:
Set time:
Press the up
or down
day.
3. Press the scroll
button again; the display will show:
Interval:4 Days
Press the up
or down
of days between regenerations.
4. Press the scroll
button again; the display will show:
Exit
Press the up
or down
into the NOVRAM® and exit the programming mode.
The regeneration cycle is necessary to wash out
impurities that are captured in the filter media during the
service cycle, and to prevent 'caking' of the filter media,
which may result in an increase of pressure drop over the
water filter. Typically a regeneration every 4 days should be
sufficient. In case of high flow rates, excessive water usage
or a high concentration of impurities in the incoming water,
it may be necessary to lower the number of days between
regenerations.
EN - English
ELECTRONIC CONTROL PANEL
button to set the
8:01
button to set the time of
button to set the number
button to save the settings
PROGRAMMING INSTRUCTIONS -
CONFIGURATION PARAMETERS
Before entering the programming mode, make sure that
the appliance is in the service mode.
All configuration parameters on this appliance have
been pre-programmed in the factory, to offer optimal
performance in a wide range of applications and situations.
Nevertheless it may be necessary or desirable to change any
of these parameters, to further optimize the appliances
performance or to adapt it to the specific requirements of
the installation.
In case no button is pressed in a period of 5 min, the
control panel will automatically return to the service mode;
any changes made will NOT be saved!
1. Press the scroll
display shows:
System Check
2. Within 10 sec, press the up
show:
Units:Metric
Press the up
measure (Metric or US).
3. ress the scroll
MaintInt: 24mths
Press the up
maintenance reminder function by setting the
maintenance interval, or deactivate the maintenance
reminder function.
4. Press the scroll
Cycle 1:
Press the up
of the regeneration cycle.
Press the scroll
regeneration cycle.
Cycle 1
Cycle 2
Cycle 3
Cycle 4
5. Press the scroll
Regen @
Press the up
regeneration.
6. Press the scroll
Exit
Press the up
into the NOVRAM® and exit the programming mode.
Page 10
button and hold it for 6 sec until the
button; the display will
or down
button to set the units of
button again; the display will show:
or down
button to activate the
button again; the display will show:
XX min
or down
button to set the length
button again to advance to the next
Backwash
No function
Fast rinse
No function (PF-GAC1,5 & PF-AG1,5)
button again; the display will show:
0:00
or down
button to set the time of
button again; the display will show:
or down
button to save the settings