Toshiba Carrier RAV-SP180KRT-UL Manuel D'installation page 21

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

+001111052201_00Ta.book Page 20 Friday, November 20, 2009 11:45 AM
High-Wall Type
Conduit Cover
Conduit hole
(dia. 7/8" (22.2 mm))
Insert remote controller wires
5. Clamp the wired remote controller wire with
the cord clamp.
6. Install the clamp base with a screw.
7. Remove the conduit cover.
Conduit hole
(dia. 7/8" (22.2 mm))
8. Attach a conduit to the conduit cover with a
lock nut.
9. Take the Indoor/Outdoor connecting wire
(3 x AWG12 (polar)) and the ground wire
(1 x AWG12) out of the cable slot on the
rear panel so that it protrudes about 11.0"
(280 mm) from the conduit cover.
Indoor/Outdoor
connecting wire
11.0"
(280 mm)
10.Insert the Indoor/Outdoor connecting wire
(3 x AWG12 (polar)) fully into the terminal
block and secure it tightly with screws.
Tightening torque: 0.12 kgf•m (1.2 N•m)
Secure the ground wire (1 x AWG12) with
the ground screw.
11.Clamp the Indoor/Outdoor connecting wire
with the cord clamp.
Conduit cover
Conduit cover
– 20 –
L
L
S
1
2
12.Attach the conduit cover.
13.Attach the terminal cover, the front panel
and the air inlet grille to the indoor unit.
CAUTION
• Be sure to refer to the wiring diagram attached
inside the front panel.
• Check local electrical cords and also any
specific wiring instructions and limitations.
• Do not catch the wired remote controller wire
when installing the clamp base
• Beware of the metal plate edge when working
on the unit. The edge can be sharp and may cut
your hand.
• Firmly tighten the screws of the terminal block.
Keep the wire length as shown in figure below when
it is connected to the terminal block.
Indoor/Outdoor unit
connecting wire
Installation Manual
Terminal
block for
indoor/
outdoor
connecting
Ground
screw
Ground
wire
Cord clamp
Indoor/Outdoor
connecting wire
EN
20-EN
Toshiba

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Rav-sp240krt-ul

Table des Matières