Setup Functions; Settings & Options - Honeywell RedLINK Manuel D'installation

Masquer les pouces Voir aussi pour RedLINK:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installer setup tables

Setup functions

0
Zone number
1
System type
2
Changeover valve
(O/B terminal)
3
Fan control
(conventional heat)
5
Stage 1 heat cycle
rate (CPH= cycles
per hour)
6
Stage 2 heat
cycle rate (CPH)
7
Stage 3 heat
cycle rate (CPH)
8
Emergency heat
cycle rate (CPH)
9
Stage 1 compres-
sor cycle rate
10
Stage 2 compres-
sor cycle rate
12
Manual/Auto
changeover
13
Adaptive Intelligent
Recovery
14
Temperature
display
Español: vea la página 20 • Français : voir la page 39
Settings & Options
0 No zoning (single thermostat used with THM5320R EIM)
[Options: select zone 1, 2, 3 or 4]
0 1 heat/1 cool conventional
1 1 heat/1 cool heat pump (no aux. heat)
2 Heat only (includes Series 20)
3 Heat only with fan
4 Cool only
5 2 heat/1 cool heat pump
6 2 heat/2 cool conventional
7 2 heat/1 cool conventional
8 1 heat/2 cool conventional
9 2 heat/2 cool heat pump
10 3 heat/2 cool heat pump
0 O/B terminal controls valve in cooling
1 O/B terminal controls valve in heating
0 Gas/Oil heat (equipment controls fan)
1 Electric furnace (thermostat controls fan)
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
9 Electric furnace
[Cycle rate options: 1 to 12 CPH]
3 Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
3 Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
0 Manual (User options: Heat/Cool/Off)
1 Automatic (User options: Heat/Cool/Auto/Off)
Applies only to Model TH6320
0 Off
1 On
0 Fahrenheit
1 Celsius
9
(factory default in bold)