1. TECHNICAL DATA

1.1.

Burner performance

Type
Oil throughput (kg/h) Burner output (kW)
BMV3
1.4 - 4.1
BMV4
1.4 - 4.1
BMV 5
3.2 - 4.7
* Specifications for units with a low pressure furnace and an exhaust
gas loss of approx. 8%.
1.2.

Certification

• DIN EN 267:1999-11: register number: 5G966/11
• Class 3 emission limits (only HL60 E/FLV.2-S)
• German ecolabel "Blue Angel" according to RAL-ZU 9: Con-
tract no. 14415 (only HL60 E/FLV.2-S)
1.3.

Operating range

• In the chart, you find allowed combustion chamber pressure
as function of the oil flow (see fig. 4).
• The operating ranges have been determined on a test-
ing unit and refer to an altitude of approx. 100 m above
sea-level and a room temperature of approx. 20°C. The
oil flow that can be achieved in practice depends on the
starting resistance of the heater.
• The starting resistance is influenced by the combustion
chamber, the flue gas line and the starting load. Exact values
can therefore only be determined on each respective system.
1.4.

Fuel

• Fuel oil EL according to DIN 51603-1
• Heating oil EL, low sulphur, according to DIN 51603-1
• Fuel oil EL A Bio 10 (bio fuel oil according to DIN SPEC
51603-6, fuel oil EL, low sulphur, with up to 10% of FAME
according to the quality requirements of DIN 14214)
1.5.

Electrical data

Nominal voltage ...................................................................230 V ~ 50 Hz
Starting power ................................................................................ca. 435 W
Operating power ..............................................................ca. 135 - 235 W
Contact rating of the thermostats and switches, ......min. 6A~
1.6.

Burner dimensions

Specifications of dimensions in mm (see fig. 5 + 6)
Packing .............................................................l 370 / w 350 / h 485 mm
Transport weight ................................................................................14.5 kg
1.7.

Acoustic emissions

The sound pressure level at maximum burner performance
is 57 dB(A).
The measurements were carried out with an accuracy class
2 measuring device according to IEC 60651 at a (horizontal)
distance of 2m.
1.8.

Burner components

Item
Motor
Oil pump
Oil pre-heater
Ignition unit
Photocell
Automatic oil firing unit
16 - 48
16 - 48
38 - 56
Make
Ref
Hanning
O1A095-030
Danfoss
BFP 21 L3
Danfoss
FPHE 5
Cofi
TRK2-40SHK
Danfoss
LDS 057H7097
Siemens
LOA 24.171B27
BMV3 / BMV4 / BMV5 : 662Y1000 • A
0,6
0,5
0,4
0,3
BMV3 / BMV4
0,2
0,1
0
0
1,0
2,0
3,0
Oil mass flow in kg/h
Débit de oul en kg/h

Figure 4

Figure 5
Figure 6
BMV5
4,0
5,0
6,0
7,0
en
3
EN
FR
NL
ES
IT
DE
PL
RU