Zephyr Essentials Cypress AK7836BS Guide D'utilisation, D'entretien Et D'installation page 28

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALL THE DAMPER
TO CENTRAL SYSTEM
RETURN AIR OR INTERIOR
WALL REGISTER
AIR FLOW
Install the damper as shown. Make sure damper flap is in a verti-
cal position when closed and power is off. The set screw can be
used to adjust the damper opening - thereby balancing the inside
and outside air pressure when the range hood exhausts at high
speed.
PRESSURE SWITCH
OPERATION
The pressure switch is designed to operate when the static
pressure increases to 0.05" Ps or more. It may not operate at low
speeds since the pressure is below this limit.
MULTIPLE DAMPERS
More than one damper may be required to balance the system.
If more than one is required use (1) MUA006A, MUA008A, or
MUA010A and then use the 54060012 (6"), 54060013 (8"), or
54060014 (10") dampers as additional dampers.
SET SCREW
OUTSIDE AIR
AIR FLOW
DAMPER FLAP (Install in
vertical position shown.)
MODELS MUA006A • MUA008A • MUA010A
INSTALLATION OF
PRESSURE SWITCH AND
PROBE
For the probe & pressure switch to work effectively the roof or
wall cap must have a spring loaded damper.
Page 5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Cypress ak7842bsCypress ak7848bsCypress ak7854bs

Table des Matières