Commissioning report T2Blue
Installer
Date of commissioning
Name of installer
Street
Postcode / city
Phone (offi ce)
Fax
Website
Project data
Customer name/address
Heater (type)
Room type
Heating circuit
Insulation resistance*
Heating cable
resistance** (Ω)
Current*** (A)
Circuit breaker (characteristic C, max 16 A)
*
Fig. 1a, 1b, 4a, 4b, 8a, 8b see installation instruction T2Blue. Test voltage > 500 Vdc (max. 2500 Vdc), result >10 MΩ
**
compare measured resistance value with reference table page 46 and 48.
*** Energise laid heating cable when connection kit has been installed. Heating cable may not be covered e.g. by fl oor
tiles, laminate etc. during measurements. Measure the current after 15 min. with doors and windows closed.
Remark: Tyco Thermal Controls requires the use of a 30 mA RCD (residual current device) to provide maximum electri-
cal protection for user safety. Please return this completed report and drawing by mail or by fax to the addresses as
indicated on last page.
10 W/m
2
m
Number
Heating cable length (m)
Before heating cable installation
(MΩ) fi g. 1a, page 40
After heating cable installation
(MΩ) fi g. 4a, page 42
After fl oor covering
(MΩ) fi g. 8a, page 44
fi g. 1b, page 40
fi g. 4b, page 42
fi g. 8b, page 45
Company
Phone (mobile)
e-mail
20 W/m
fl oor covering (tile/carpet)
rated voltage (V)
Heating cable
1
Heating cable
Heating cable
2
3
9