3
TECHNICAL SPECIFICATIONS
3.3
Input/Output Connections and User Display
Sealing
Studs
Figure 4 - Mini Meter Connections and Display
Voltage Inputs (wire connections)
L1
N
L2
CT Inputs
CT1 : X1
CT1 : X2
CT2 : X1
CT2 : X2
Isolated Output
CT1
CT2
L1
N
L2
X1 X2
X1 X2 10 100 1000
Table 2A - Input Connections
9
(Kh) Isol
Counter
COM
1 2
Description
Black wire, voltage input, Line 1,120 V with
respect to neutral
White wire, Neutral input
Red wire, voltage input, Line 2, 120 V with
respect to neutral (MMD models only)
Current Transformer input, CT1. Black or
Wh/Blk (striped) wire of CT1
Current Transformer input, CT1. White wire
of CT1
Current Transformer input, CT2. Red or
Wh/Rd (striped) wire of CT2 (MMD
models only)
Current Transformer input, CT2. White wire
of CT2 (MMD models only)
LCD
Display
Load
LED