3
TECHNICAL SPECIFICATIONS
3.2
Electrical and Environmental Specifications
Mini Meters fall under UL Circuit Category III: a device for measurements performed
in the building installation. The electrical and environmental specifications for Mini
Meters are given in the table below
Input Configurations
Supply Voltage Range
(L1 or L2 to Neutral)
Maximum Input Power
Maximum Rated Current
Line Frequency
Power Factor Range
Accuracy
Operating Temperature Range
Rated Pollution Degree
Rated Relative Humidity
Branch Fuse Holder
Klemsan ASK2 or equiv.
Branch Fuses
Large/XL Enclosure: Littlefuse, Inc.
0235003.HXP or equiv.
Medium Enclosure: Littlefuse, Inc.
0235001.HXP or equiv.
Terminal Blocks Mini Meter
Dinkle/International Connector
EK508-11P or equiv.
MMU: Molex 0387800105 or Cinch Barrier
Block Series 141 or equiv.
Table 1 - Electrical and Environmental Specifications
1
Product approved for use with included Leviton Current Transformers, as follows:
• 200A: Part Numbers CDA02-x12 (CDA02-B12, CDA02-R12, CDA02-L12, CDA02-212,
CDA02-312) for Solid Core, 0.72" Diameter CTs or CTD02-K16 for Split Core 1" CTs
• 100A: Part Numbers CDA01-x12 (CDA01-B12, CDA01-R12, CDA01-L12, CDA01-212,
CDA01-312) for Solid Core, 0.72" Diameter CTs or CTD01-K16 for Split Core 1" CTs
2
Pollution Degree 2: normally only non-conductive pollution occurs. Occasionally, however,
a temporary conductivity caused by condensation must be expected.
1 Phase, 2 wire
1 or 2 Phase, 3 wire
Min. 102 VAC Max. 138 VAC
8 VA
220 A primary for 200 A models
1
110 A primary for 100 A models
0.11 A secondary for 0.1 A secondary models
0.22 A secondary for 0.2 A secondary models
50-60 Hz
0.5 to 1.0, leading or lagging
+/- 0.5% of registration @ 1.0pf. 2 to 200 A
+/- 0.75% of registration @ 0.5pf, 2 to 200 A
-30 to +70 degrees C
2
2
80%
500 V, 6.3 A, 6 mm2
250 V, 3 A, fast acting, short time lag
250 V, 1 A, fast acting, short time lag
4.4 in-lb of torque maximum
12 in-lb of torque maximum
8