Installation

CAUTION
Risk of injury due to pressurised liquid
If installation, removal or maintenance work is not carried out correctly, there is a risk of injuries at the connection points, if pressurised
water suddenly escapes.
Ensure proper installation, removal or maintenance work.
Ensure that the system is de-pressurised before performing installation, removal or maintenance work at the connection points.
CAUTION
Risk of injury due to falls or bumps
Bruising from falls or bumps on system components during installation.
Wear personal protective equipment (helmet, protective clothing, gloves, safety boots).
Note the following for installation:
Comply with the local installation regulations.
Ensure easy access at the location of installation.
Protected from flooding and frost.
Always install the fitting downstream of a system isolator.
Ensure the correct direction of flow through the components.
The arrow markings on the components indicate the correct direction of flow.
Ensure the correct position of the fitting within the make-up line.
Horizontal position of the filter head.
Vertical position of the filter housing.
Use Teflon tape to seal the thread connection when flat gaskets are not intended.
If necessary, use the supplied bracket to support the fitting.
Ensure a stress-free installation of the fitting.
Reflex Fillsoft — 20.01.2017-Rev. B
Installation
English — 7