4
Installation and assembly
CAUTION
Risk of burns
Escaping hot medium can cause burns.
•
Maintain a sufficient distance from the escaping medium.
•
Wear suitable personal protective equipment (safety gloves and goggles).
4.1
Notes
The following items must be considered when assembling and installing the equipment:
•
Do not install the device above sensitive components or close to electrical plant.
•
Perform installation in dry and frost-proof locations.
•
The flow direction is not pre-determined.
•
The component can be installed horizontally or vertically.
•
When installing ensure there are no residual stresses.
–
Any stresses that may occur in some cases must be countered by appropriate constructive actions. Stresses may be caused by
temperature effects, for example.
•
Ensure the device is readily accessible in its place of installation.
•
Ensure sufficient bearing capability of the installation site.
–
This applies to filling the separator with water in particular.
–
If necessary additional structural measures may be required to ensure adequate load bearing capacity.
•
The device is not a load-bearing structural element.
–
By default, the calculation of the vessels does not take lateral acceleration forces into account. Avoid alternating stresses such
as pressure shocks, abrupt pressure changes, or strong vibrations.
•
Use only approved transport and lifting equipment.
•
The angle of the lifting tackles must be maximum 60°.
•
After attachment of insulation, attach the additional sticker on the outside so that it is readily visible.
•
Flush the system thoroughly after installation.
Note!
•
For horizontal component installation we recommend positioning the magnet so that it can be removed towards the
front. (See draining and venting function).
-
Easier handling for cleaning and maintenance.
-
Reduced leakage during cleaning and maintenance.
•
Observe the correct positioning of the add-on components such as drain, venting plug and blanking plug so that they
function correctly for the selected horizontal or vertical installation.
•
We recommend fitting shut-off valves upstream and downstream of the device to simplify maintenance.
Note!
•
Attach the magnetic field warning sticker on the device so that it is clearly visible.
–
The warning sticker is included in the scope of delivery.
4.2
Space requirements
The space below the separator must at least correspond to the diameter of the component and must be chosen so that it is possible to
remove the magnetic insert and sacrificial anode.
Exdirt magneto — 19.06.2017
Installation and assembly
English — 9