System Volts ........................... 12 V
PWM Setpoint ......................... 14.1 V
Max. Solar Volts ...................... 30 V
Accuracy .................................. 60 mV
Rated Solar Input .................... 4.5 A
Min. Operating Volts .............. 6 V
Max. Input (5 min.) ................. 5.5 A
Self-consumption .................... 6 mA
1. SunGuard can be mounted in any position. It is best to mount to a vertical surface
and allow space for air flow through the controller.
2. First connect the Battery BLACK wire (negative) to the battery. Use either black
wire since they are connected together inside the controller.
3. Connect the RED Battery positive wire to the battery.
4. Connect the Solar array using the other BLACK wire and the YELLOW Solar
positive wire. Be very careful not to short circuit the solar array, or the controller
will be damaged.
5. SunGuard prevents reverse current leakage at night, so a blocking diode is not
required in the system.
6. A negative earth ground at the battery is recommended for most effective
lightning protection.
7. SunGuard can be mounted outdoors. Do not expose to ambient temperatures
above 60°C. Make sure that water will drain from inside the case.
SPECIFICATION SUMMARY
INSTALLATION
2
Max. Solar Short Circuit
Rating ................................5.5 A
PWM Temp
Compensation ..................–28 mV/°C
Reverse Current Leakage ..<10 A
Ambient Temperature
Range ................................–40 to +60°C
Relative Humidity ............100%