Function/Configuration
LEVEL SWITCH 8112 - with relay output
6 Set up
6.1 In general
The numbers in brackets refer to the following illustrations.
The switching condition of the electronics can be checked with
closed housing cover (control lamp). In the basic setting,
products with a density >0.7 g/cm³ (0.025 lbs/in³) can be
detected. For products with lower density, the switch must be
set to >0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following indicating
and adjustment elements:
Signal lamp (1)
l
DIL switch for mode adjustment - A/B (2)
l
DIL switch for sensitivity adjustment (3)
l
Note:
For test purposes, immerse the tuning fork of LEVEL SWITCH
8112 always in liquids. Do not test the function of LEVEL
SWITCH 8112 with the hand. This can damage the sensor.
6.2 Adjustment elements
Fig. 12: Oscillator SWE60R - Relay output
1
Signal lamp (LED)
2
DIL switch for mode adjustment
3
DIL switch for sensitivity adjustment
Set up
1
2
3
19