Electronics and connection
compartment
LEVEL SWITCH 8112 - with relay output
1 Unscrew the housing cover
2 Loosen compression nut of the cable entry
3 Remove approx. 10 cm (4 in) of the cable mantle, strip
approx. 1 cm (0.4 in) insulation from the ends of the
individual wires
4 Insert the cable into the sensor through the cable entry
5 Open the terminals with a screwdriver
6 Insert the wire ends into the open terminals according to
the wiring plan
7 Tighten the terminals with a screwdriver
8 Check the hold of the wires in the terminals by lightly
pulling on them
9 Tighten the compression nut of the cable entry. The seal
ring must completely encircle the cable
10 Screw the housing cover back on
The electrical connection is finished.
5.3 Wiring plan, single chamber housing
2 0 - 2 5 3 V A C
5
Fig. 10: Electronics and connection compartment, single chamber housing
1
Control lamp
2
DIL switch for mode adjustment
3
DIL switch for switching point adaptation
4
Ground terminal
5
Screwed terminals
Connecting to power supply
SW E60R
0,5 g / cm 3
3 4 5 6 7 8
A
2 0 - 7 2 V D C
+
0,7 g / cm 3
B
L
N
1 2
3 4 5
6 7 8
1
2
3
4
17