3.4.4 – Fault mode.
The unit is in fault mode when there is a fault in any of the areas.
Acoustic warning: The module activates an intermittent acoustic warning.
Visual warning: The amber fault LED will remain lit and the display will show a code
indicating the type of fault. If the display does not show the fault code, because it is
showing the CO PPM, press key A.
3.4.5 – Test mode.
GB
The system allows functioning in test mode, to be able to revise the installation easily.
If you press keys C and D at the same time, the system will go into test mode.
You can trip the detectors without the relays being activated.
The detector will light up the LED continuously. Once you have checked that the
detector has been tripped, move on to the next detector.
If you press keys C and D again, the unit comes out of test mode. Once out, the
detectors will be reset.
If you press keys A and B at the same time, the unit will go into counter consultation
and configuration mode.
1st Press: selects alarm relay configuration.
2nd Press: alarms counter.
3rd Press: extraction 2 counter.
4th Press: extraction 1 counter.
3.5.1- Configuring the alarm relay.
You have the option of configuring the alarm relay to be activated when there is a fault
in the system.
To do this, proceed as follows.
Press keys A and B at the same time.
The fault LED will blink.
With button C, select YES or NO.
In YES mode, the alarm relay will be activated if there is a fault.
In NO mode, the alarm relay will not be activated if there is a fault.
If you press keys A and B 4 times in a row you will exit the relay configuration.

3.5- Configuration and counters