Nom de variable
données
790.0
ConstPerfWs6
794.0
ConstPerfWs7
798.0
ConstPerfWs8
802.0
WinCC_exist
802.1
P_Cont_Mode
802.2
P_Cont_FltMode
804.0
P_Cont_TimeInvOrder
808.0
P_Cont_Threshold_LL
812.0
P_Cont_Threshold_HL
816.0
P_Cont_Max_Time
820.0
P_Cont_Min_Time
824.0
P_Cont_Hysteresis
828.0
P_Cont_InvSpare
830.0
P_Cont_DeadBand
834.0
CosPhi_Cont_DeadBand
838.0
Q_Cont_Auto
840.0
Q_Cont_U_Hys
844.0
Q_Cont_U1Ind
848.0
Q_Cont_U2Ind
852.0
Q_Cont_U_Ind_h
856.0
Q_Cont_Q_Max_Ind
860.0
Q_Cont_U1Cap
864.0
Q_Cont_U2Cap
868.0
Q_Cont_U_Cap_I
872.0
Q_Cont_Q_Max_Cap
876.0
Q_Cont_Timer_U_lim
880.0
Q_Ramp_LockUp
880.1
Q_Ramp_LockDn
882.0
Q_Ramp_TimeUp
886.0
Q_Ramp_TimeDn
PVS ControlBox 300
Instructions de service, 01/2013, A5E03642519A/003
Type de
Désignation
données
REAL
constant Wp for performance
ratio weatherstation 6
REAL
constant Wp for performance
ratio weatherstation 7
REAL
constant Wp for performance
ratio weatherstation 8
BOOL
WinCC exists in plant
BOOL
Controller Mode
BOOL
Controller Fault Mode
TOD
Controller Time to set Inverter
Order
REAL
Controller Threshold Minimum
REAL
Controller Threshold Maximum
REAL
Controller Timer Inverter
Maximize
REAL
Controller Timer Inverter
Minimize
REAL
Controller Hysteresis
INT
Controller Inverter Spare
REAL
Deadband active power PI
controller
REAL
Deadband cos(Phi) PI controller
BOOL
Q controller automatic switch
REAL
Hystersis U
REAL
Linear slope : U
REAL
Linear slope : U
REAL
U:prot: Shutdown level
REAL
Max. sustainable ind. reactive
power
REAL
Linear slope : U
REAL
Linear slope : U
REAL
U:prot: Shutdown level
REAL
Max. sustainable cap. reactive
power
REAL
Delay time for reaction on limits
for under voltage protection and
over voltage protection
BOOL
Q ramp locked ramp up
BOOL
Q ramp locked ramp down
REAL
Q ramp time up to get value [s]
REAL
Q ramp time down to get value
[s]
8.5 Interface de paramètres de la régulation du parc
Valeur
par
défaut
2000.0
2000.0
2000.0
0
0
1
TOD#0:0:
0:0
0.0
100.0
2.0
2.0
1.0
1
0.1
0.001
false
0.1
at Q
=0
21.4
1
1
at Q=Q
21.65
2
max
21.8
0.0
at Q=0
0
1
at Q=Q
0
2
max
0
0.0
60.0
false
false
30.0
30.0
Logiciel
Accès
Champ
obligatoire
Lecture/
écriture
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non
r / w
Non