I/O Connections

The I/O terminals are located in the center of
4.
the wiring compartment, as shown previously
in Figure 9.
The Digital Input connections (I1 and I2) are used to
control the Drive based on the state of an external
device, such as a flow switch, moisture sensor,
alternator, or other device. Programming is needed
to activate any of these functions (see Table 5).
The Output Relay (O1) is used to control an external
device based on two states of Drive; either Running
the pump or Faulted. Programming is needed to
activate any of these functions (see Table 5).

Cable Installation

Three 1/2" conduit knockouts are provided on the
bottom of the Drive enclosure for the I/O wires.
Break out the closest 1/2" knockout and route the
wires through. Use a cord grip to prevent the wire
from rubbing and causing a short.
NOTICE Never run low voltage I/O wire through
the same conduit hole as the 230V input wires or
motor wires.
To connect the external wires to the terminals:
1. Strip wire ½ inch
2. Push spring terminal up with finger or slotted
screwdriver
3. Insert wires from bottom
4. Release spring terminal

Connection Examples

Figures 15-18 show various connection schemes
for typical applications. Table 6 describes each I/O
terminal, including purpose and rating.
Figure 15 - Example Input with internal 24 volt
supply
115 VAC
or
230 VAC
Figure 16 - Example external Input with
external supply
Figure 17 - Example Output relay with internal 
24 volt supply
+
115 VAC
or
230 VAC
-
Figure 18 - Example Output relay with
external supply
+
-
6540 0412
16