You can choose different possibilities for the priority of
the tank loading. See the parameters priority tank "PR
Tk" for more information.
3.2.3 System 3.
System with 2 tanks, 2 pumps, 1 collectors array and
3 sensors.
With this system you can add an extra function with
1 sensor T4 (PT1000) (Thermostat, Cooling, Antista-
gnation).
T1
P2
P1
The loading of the tanks is authorized if the temperature
difference "dt" between the collector (T1) and the tanks
(T2, T3) is sufficient.
You can choose different possibilities for the priority of
the tank loading. See the parameters priority tank "PR
Tk" for more information.
T3
T2
3.2.4 System 4.
System with 1 tank, 1 pump, 1 valve, 2 collector arrays
with 2 different cardinal direction (ie. East / West) and
3 sensors. With this system you can add an extra fun-
ction with 1 sensor T3 (NTC) (Thermostat, Cooling,
Antistagnation).
T1
P2
P1
The loading of the tank1 is authorized if the temperature
difference "dt" between collector (T1, T4) and the tank1
(T2) is sufficient. The valve direction (P2) is done by the
warmer collector.
3.2.5 System 5.
System with 1 collector array, 1 solar tank, 2 pump. With
this system you can not add an extra function.
T1
P1
This system allows warming the hot water by solar tank 1
or by two additional boilers. The P2 and P3 contacts are
used to do this function. You will have the possibility to
adjust different levels for loading priority.
See the parameters "DHW" for domestic hot water hot
water temperature, "LEGI" for legionellisis.
28
T4
T2
T3
P3
P2
T2