Télécharger Imprimer la page

Danfoss KP 7ABS Instructions page 3

Masquer les pouces Voir aussi pour KP 7ABS:

Publicité

Technical data
Permissible ambient temperature
–25°C to +65°C (+80°C for max. 2 h)
Range: 8 → 32 bar (p
)
e
Relative humidity: 30 to 98 %
Vibration resistance: 4g (10 to 1000 Hz)
Max. permissible test pressure: 35 bar (p
Max. working pressure: 35 bar (p
Enclosure
In accordance with EN 60529:
IP 30 (VDE).
It is assumed that the control will be
mounted on a smooth panel or bracket. The
bracket must be positioned on the unit so
that all clear holes are covered. See g. 13.
Contact load
See the S scale in the control.
Max. start current = 112 A, 380 V.
Short circuit protection: Fuse 16Amp.
Application in accordance with UL-
requirements:
120 V a.c.: 16 FLA, 96 LRA
240 V a.c.: 8 FLA, 48 LRA
240 V d.c.: 12 W pilot duty
Fitting
The KP 7BS is tted with a damping ori ce.
It is therefore not usually necessary to use
damping coils. The KP 7BS is connected
with 1/4 in. copper tube.
Figs. 2 and 3
As far as possible, position the control
above the plant piping system.
A mounting bracket can be supplied. See
g. 12.
Avoid connection in or near liquid pockets.
Fig. 4
When tightening or loosening the are
coupling, hold the connector steady by
applying a counterforce.
Electrical connection
Fig. 5
The control is equipped with a cable entry
for 6 - 14 mm cable (15, g. 1). This Pg 13.5
entry can be obtained as an accessory ( g.
14).
Use terminals B and C.
The order in which they are used is not
important.
Terminal A must not be used.
Testing
Fig. 6
S side
Tilt the main arm (3). At the same time
operate the internal RESET button
Fig. 7
B side
Tilt the arm (19) with, for example, a screw-
driver. At the same time operate the
3
external RESET button. Be careful not to
damage the bellows with the screwdriver!
NOTE! Use only the methods shown when
testing.
The contact system must never be activated
)
with a screwdriver or similar tool.
e
)
e
Setting
Fig. 8
Set the stop pressure on the STOP scales.
Check the set pressure with a pressure
gauge. Set the S side 2 - 3 bar higher than
the B side. The di erential is xed at approx.
4 bar.
The compressor motor can be restarted after
stop by pressing the RESET buttons. Restart
is possible only when the pressure has fallen
approx. 4 bar under the set stop pressure.
Fig. 9
Setting example.
Required stop pressure = 13 bar (p
Di erential = 4 bar.
The compressor can be restart when the
pressure has fallen to 13 – 4 = 9 bar. Set the
required stop pressure.
Fig. 10
Locking the setting.
The range spindles can be locked with the
locking plates.
Fig. 11
Locking and sealing.
Accessories
Fig. 12
Two types of mounting brackets (wall
bracket and angle bracket) complete with
screws and washers can be supplied.
Fig. 13
Positioning the angle bracket.
Fig. 14
Pg 13.5 screwed cable entry with special
nut. To be ordered separately. For use with
6 - 14 mm cable.
With 8-16 mm cable use a standard Pg 16
screwed cable entry.
Doppel-Hochdruckschalter
Vom TÜV
(Technischer
Verein) gemäß EN 12263
B = Druckbegrenzer
S = Sicherheitsdruckbegrenzer
In Übereinstimmung mit EN 12263 bewirkt
ein Bruch der Hochdruckwellrohre (innere
Wellrohre) des Geräts ein Ausschalten des
Kompressors der Kälteanlage. Der Kompres-
sor kann darauf erst nach einer Auswechs-
lung des Pressostats wiedereingeschaltet
werden. Bei einem Bruch am äusseren Well-
rohr fällt der Ausschaltdruck des Geräts um
ca. 3 bar unter den Einstellwert ab. Somit
schaltet das Gerät bei normalem Ver us-
sigerdruck aus. Dadurch ergibt sich eine
)
störungssichere Funktion (fall safe).
e
Die B-Seite kann mit einem aussenseitigem
Resetknopf wieder eingeschaltet werden,
wenn der Druck um ca. 4 bar unter den Soll-
wert des Ausschaltdruckos abgefallen ist.
Die S-Seite kann mit einem innenseitigen
Resetknopf wieder eingeschaltet werden,
wenn der Druck um ca. 4 bar unter den Soll-
wert des Ausschaltdruckes abgefallen ist.
Fig. 1
1.
Bereichspindel, S-Seite
3.
Haupthebel
5.
Bereichspindel, B-Seite
15.
Kabeldurchfuhrung
18.
Sperrplane
19.
Hebel
Technische Daten
Zulässige Umgebungstemperatur:
–25°C bis +65°C (+80°C max. 2 Stunden)
Bereich: 8 - 32 bar (p
Relative Feuchtigkeit: 30 bis 98%
Vibrationsfestigkeit: 4g (10 bis 1000 Hz)
Max. zulässiger Prüfdruck: 35 bar (p
Max. zulässiger Betriebsdruck: 35 bar (p
Kapselung und Schutzart
Gemäß EN 60529: IP 30 (VDE).
Als Voraussetzung gilt, daß das Gerat auf
einer ebenen Tafel oder auf einer Konsole
montiert wird. Das Gerat ist auf der Konsole
so anzuordnen, daß alle freien Ö nungen
abgedeckt sind.
Siehe Fig. 13.
Kontaktbelastung
Siehe S-Skala des Geräts.
Max. Anlaufstrom = 112 A, 380 V.
Kurzschluss-Schutz: Sicherung 16 Amp
Anwendung gemäß UL-Bedingungen
120 V a.c.: 16 FLA, 96 LRA
240 V a.c.: 8 FLA, 48 LRA
240 V d.c.: 12 W Steuerstrohm
DKRCCPICAOB157-520H1364
©Danfoss A/S
DEUTSCH
Überwachungs
)
e
)
e
)
e

Publicité

loading

Ce manuel est également adapté pour:

Kp 7bs