SiGnal allows selecting
the setpoint output in volts or mA.
Press both keys to switch over from
SiGn to ou.Lo and ou.HI.
–
output.Low allows defi-
ning the lowest value.
–
output.High allows defi-
ning the highest value.
Use the left key to select the decade
and the right key to select a value
from 0 ... 9.
During operation, it is not possible to
define a value lower than the ou.Lo
value or higher than the ou.Hi value.
The default value for ou.Lo is 0 V or
0 mA. The default value for ou.Hi is
12 V or 24 mA.
2. After setting the value of ou.Hi,
press both keys; the following
message is displayed:
3. Use the right key to select YES or
no
⇑
4. If YES is selected, press both
keys simultaneously to end the
programming. The new values are
saved in the EEPROM.
⇑
⇑
5. The device is ready for operation.
6
6. If, during operation, the operator
switches to the programming mode
and alters the parameters ou.Lo.
or ou.Hi, take into account the fol-
lowing when exiting the program-
ming mode:
If the value of parameter ou.Lo
was altered, the output of the devi-
ce will automatically be set to the
value of parameter ou.Lo when it
will be set back to operation.
If the value of parameter ou.Hi
was altered, the output of the devi-
ce will automatically be set to the
value of parameter ou.Lo when it
will be set back to operation.
4.2.2 Operating Mode MAn
1. The following parameters can be
programmed for the MAn mode:
⇑
⇑
⇑
A
see page 9
to
for mA 24
bei mA 24.00
to
for mA 24
bei mA 24.00
to