sauter NRT405F901 Instructions page 4

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

B
Figure 5: Connection diagram
B
Figure 6: Connection diagram
40
DI
L
10
41
AGnd
11
°C
42
AI
N
12
°C
43
UI
N
13
44 AGnd
DO1
20
50
DO2
21
51
DO3
22
52
30
53
54
DO4
31
B
CDO45
32
DO5
33
Figure 7: Connection diagram with electric heater
40
DI
L
10
41
AGnd
11
°C
42
AI
N
12
°C
43
UI
N
13
44 AGnd
DO1
20
I
II
50
DO2
21
III
51
DO3
22
52
53
30
54
DO4
31
B
CDO45
32
DO5
33
Figure 8: Connection diagram with a solid state relay for electric heater
Connection of different actuators
When connecting thermal actuators, DO4 is used for heating actuators
and DO5 for cooling actuators. If the installation is a 2-pipe installation
and the change-over function is used, the actuator should be connected
to DO4.
When connecting 3-point actuators, DO4 is used for increase signal and
DO5 for decrease signal, even when the change-over function is used.
NRT405F901
L
10
L
230 V AC
N
11
-
12
N
13
N
20
DO1
I
II
M
III
21
DO2
22
DO3
ELECTRIC
HEATER
30
-
31
DO4
32
CDO45
L
230 V AC
N
33
DO5
40
DI
M
41
Agnd
Solid state relay
42
AI
1 2 U 3 4 U
I I
43
UI
ELECTRIC HEATER
44
Agnd
50
Agnd
51
-
52
-
53
A
54
B
*The sum of the current through DO1-DO3 is protected by a fuse
230 V AC Line
Power supply
Not connected
230 V AC Neutral
Power supply (internally con-
nected to terminal 13)
Fan-coil common /
Common fan-coil connec-
230 V AC Neutral
tor (internally connected to
terminal 12)
Fan-coil output 1
Relay, 230 V AC*, 3 A
for fan control
Fan-coil output 2
Relay, 230 V AC*, 3 A
for fan control
Fan-coil output 3
Relay, 230 V AC*, 3 A
for fan control
Not connected
Digital output 4 for
Digital output. 230 V AC, max
heating/cooling
300 mA. Max 2 A during 20
or opening with
ms.
3-point actuator
Common DO4 & 5
Common connection for
digital outputs 4 and 5
Digital output 5 for
Digital output. 230 V AC, max
cooling or clos-
300 mA. Max 2 A during
ing with 3-point
20 ms.
actuator. Heating/
cooling when
electrical heater is
configured
Digital input
Potential-free window contact
or occupancy contact. Con-
figurable for NO/NC.
Analogue ground
Analogue input
External PT1000 instead of
the internal NTC
Universal input
Change-over input. Potential-
free switch (configurable for
NO/NC) or PT1000.
Analogue ground
Analogue ground
Not connected
Not connected
RS485 communication A
RS485 communication B
4