sauter NRT405F901 Instructions page 3

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Description
12
Switch on delay for Comfort mode
13
Sensor connected to AI1:
0=Internal sensor, 1=External room sensor
14
Sensor connected to UI1:
0=None, 1=Change-over digital, 2=Change-over
analogue
15
Type of digital actuator:
0=Thermal, 1=3-point
16-
Not used for this model
17
18
Period time for heating actuator with
thermal actuator
19
Period time for cooling actuator with
thermal actuator
20
Runtime for heating actuator with increase/de-
crease actuator
21
Runtime for cooling actuator with increase/de-
crease actuator
22
Time in hours between exercise of heating actua-
tor
23
Time in hours between exercise of cooling actua-
tor
24
Setpoint or actual value shown in the display:
0=Actual, setpoint when changing the setpoint,
1=Actual, setpoint adjustment when changing the
setpoint, 2=Setpoint, 3=Only the setpoint adjust-
ment
25
Configuration of fan control:
0=No control, 1=The fan is controlled by heating
requirement, 2=The fan is controlled by cooling
requirement, 3=The fan is controlled by heating
and cooling requirement
When using an electric heater, this parameter
should only be set to 1 or 3, or the heater may be
overheated.
26
Start signal in % of the controller output, heating
or cooling, for fan speed 1
27
Start signal in % of the controller output, heating
or cooling, for fan speed 2
FS
Description
0 min
28
Start signal in % of the controller output, heating
or cooling, for fan speed 3
0
29
Hysteresis for start/stop of fans in % of the control-
ler output.
0
30
Number of fan speeds
31
Fan speed in the Auto mode:
0
0=The fan speed follows the cooling/heating
output, 1=The fan speed is minimum limited to
the lowest speed
32
Temperature compensation on AI1
60 s
33
Temperature compensation for the internal room
sensor
60 s
34
Highest permitted setpoint offset upwards. Set-
table value=0...13 K. Starting point=22°C.
120 s
35
Highest permitted setpoint offset downwards. Set-
table value=0...17 K. Starting point=22°C.
120 s
36
NO/NC digital input 1:
0=NO, 1=NC
23
37
NO/NC universal input 1:
0=NO, 1=NC
23
38
NO/NC digital output 4:
0=NO, 1=NC
2
39
NO/NC digital output 5:
0=NO, 1=NC
40
Manual/Auto heating output signal:
0=Off, 1=Manual, 2=Auto
41
Manual/Auto cooling output signal:
3
0=Off, 1=Manual, 2=Auto
42
Heating output signal in manual mode
43
Cooling output signal in manual mode
44
Model
45
Version Major
46
Version Minor
47
Released or beta version
20 (5
48
Revision
when
using an
49
Display backlight low
electric
50
Display backlight high
heater)
51
PLA address
60
52
ELA address
FS
100
5
3
1
0 K
0 K
13 K
17 K
0
0
1
1
2
2
0
0
-
-
-
-
-
10
30
-
-
NRT405F901
Description
53
Modbus address
54
Modbus communication parity bit:
0=No parity, 1=Odd parity, 2=Even parity
55
Modbus timeout for character (t1.5) in ms. Should
be 1.5 times a character, i.e. at least 2 ms.
56
Modbus answer delay (t3.5) in ms. Should be 3.5
times a character, i.e. at least 5 ms.
57
Communication protocol:
0=Modbus, 1=BACnet MS/TP
58
BACnet MS/TP MAC address
0-127=master address, 128-254=slave address
59
The 4 low numbers in the BACnet device ID,
0-9999
60
The 3 high numbers in the BACnet device ID
61
BACnet MS/TP Max. master
62
Communication protocol speed:
0=9600 bps, 1=19200 bps, 2=38400 bps,
3=76800 bps (alternative 3 only applies to BAC-
net)
63
Resets communication parameters (not address-
es) to their factory settings:
1=Factory settings (Modbus@9600)
64
Basic setpoint. Settable value=5...50°C.
Wiring
10
20
30
POWER
LOGIC
40
50
Figure 4: Bottom plate connections
FS
254
2
2 ms
5 ms
0
-
-
-
127
0
0
22°C
3