Impostazione
I n
ingressi
Tipo di sonda,
segnale e scala
ingresso principale
Typ
TIPO
4 DIGIT
SONDA
senza punto dec. con punto dec.
Sensore: TC
0
TC J °C
0/1000
0.0/999.9
1
TC J °F
32/1832
32.0/999.9
2
TC K °C
0/1300
0.0/999.9
3
TC K °F
32/2372
32.0/999.9
4
TC R °C
0/1750
0.0/999.9
5
TC R °F
32/3182
32.0/999.9
6
TC S °C
0/1750
0.0/999.9
7
TC S °F
32/3182
32.0/999.9
8
TC T °C
-200/400
-199.9/400.0
9
TC T °F
-328/752
-199.9/752.0
10
TC B °C
44/1800
44.0/999.9
11
TC B °F
111/3272
111.0/999.9
12
TC E °C
-100/750
-100.0/750.0
13
TC E °F
-148/1382
-148.0/999.9
14
TC N °C
0/1300
0.0/999.9
15
TC N °F
32/2372
32.0/999.9
16
TC L °C
0/600
0.0/600.0
17
TC L °F
32/1112
32.0/999.9
18
TC U °C
-200/400
-199.9/400.0
19
TC U °F
-328/752
-199.9/752.0
20
TC G °C
0/2300
0.0/999.9
21
TC G °F
32/4172
32.0/999.9
22
TC D °C
0/2300
0.0/999.9
23
TC D °F
32/4172
32.0/999.9
24
TC C °C
0/2300
0.0/999.9
25
TC C °F
32/4172
32.0/999.9
26
TC °C
Custom
27
TC °F
Custom
Sensore: RTD
28
PT100 °C
-200/600
-199.9/600.0
29
PT100 °F
-328/1112
-199.9/999.9
30 JPT100 °C
-200/600
-199.9/600.0
31 JPT100 °F
-328/1112
-199.9/999.9
Sensore: PTC - NTC
32
PTC °C
-55/120
-55.0/120.0
33
PTC °F
-67/248
-67.0/248.0
34
NTC °C
-10/70
-10.0/70.0
35
NTC °F
14/158
14.0/158.0
Sensore: Tensione + Corr.
36
0...60mV
-1999/9999
-199.9/999.9
37
0...60mV
linear custom
linear custom
38 12...60mV
-1999/9999
-199.9/999.9
39 12...60mV
linear custom
linear custom
40
0...20mA
-1999/9999
-199.9/999.9
41
0...20mA
linear custom
linear custom
42
4...20mA
-1999/9999
-199.9/999.9
43
4...20mA
linear custom
linear custom
44
0...10V
-1999/9999
-199.9/999.9
45
0...10V
linear custom
linear custom
46
2...10V
-1999/9999
-199.9/999.9
47
2...10V
linear custom
linear custom
48
0...5V
-1999/9999
-199.9/999.9
49
0...5V
linear custom
linear custom
50
1...5V
-1999/9999
-199.9/999.9
51
1...5V
linear custom
linear custom
52
0...1V
-1999/9999
-199.9/999.9
53
0...1V
linear custom
linear custom
54 200mV...1V
-1999/9999
-199.9/999.9
55 200mV...1V
linear custom
linear custom
Sensore: Custom PT100 - PTC - NTC
56
PT100
custom
JPT
57
PTC
custom
58
NTC
custom
In caso di non disponibile i limiti minimo e massimo vengono posti a 0.
In caso di linearizzazioni Custom i limiti di test per settare gli errori LO o HI sono dati dai
valori di calibrazione.
Se questi limiti non vengono superati, vengono presi in considerazione come limiti LO_S
e HI_S.
Errore massimo di non linearità
per termocoppie (Tc),
termoresistenza (PT100) e
termistori (PTC, NTC)
L'errore è calcolato come scostamento
dal valore teorico con riferimento in %
al valore di fondo scala espresso in
gradi Celsius (°C)
• Parametri ingressi TC / LIN
3 DIGIT +segno
(Solo per mod. 96)
senza punto dec.
con punto dec.
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
-200/400
-99.9/99.9
-328/752
-99.9/99.9
non disp.
non disp.
non disp.
non disp.
-100/750
non disp.
-148/999
non disp.
0/999
non disp.
32/999
non disp.
0/600
0.0/99.9
32/999
32.0/99.9
-200/400
-99.9/99.9
-328/752
-99.9/99.9
0/999
non disp.
32/999
non disp.
0/999
non disp.
32/999
non disp.
0/999
non disp.
32/999
non disp.
Custom
Custom
Custom
Custom
Custom
Custom
-200/600
-99.9/99.9
-328/999
-99.9/99.9
-200/600
-99.9/99.9
-328/999
-99.9/99.9
-55/120
-55.0/99.9
-67/248
-67.0/99.9
-10/70
-10.0/70.0
14/158
14.0/99.9
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
custom
custom
custom
custom
custom
custom
custom
custom
custom
S, R scala 0...1750°C; errore < 0.2% f.s. (t > 300°C) / per altre scale; errore < 0.5% f.s.
T
errore < 0.2% f.s. (t > -150°C)
B
scala 44...1800°C; errore < 0.5% f.s. (t > 300°C) / scala 44,0...999,9; errore < 1% f.s. (t > 300°C)
U
scala -99,9...99,9 e -99...99°C; errore < 0.5% f.s. / per altre scale; errore < 0.2% f.s. (t > -150°C)
G
errore < 0.2% f.s. (t > 300°C)
D
errore < 0.2% f.s. (t > 200°C)
C
scala 0...2300; errore < 0.2% f.s. / per altre scale; errore < 0.5% f.s.
NTC errore < 0.5% f.s.
Tc tipo J, K, E, N, L
errore < 0.2% f.s.
PT100, JPT100 e PTC
errore < 0.2% f.s.
Selezione tempi di
campionamento
(risoluzione).
Solo per ingresso lineare
Filtro digitale ingresso
principale
Filtro digitale sulla
visualizzazione della
variabile di processo
Posizione punto decimale
per la scala ingresso
principale
Limite minimo scala
ingresso principale
e uscita analogica
Limite massimo scala
ingresso principale
e uscita analogica
Offset di correzione
ingresso principale
Selezione funzione
ingresso digitale
Selezione funzione
tasto incrementa
attivo solo in P.V.
Selezione funzione
tasto decrementa
attivo solo in P.V.
Limite inferiore
impostabilità soglie di
intercettazione
Limite superiore
impostabilità soglie di
intercettazione
5
0
120ms
> 13bit; 8000 punti
1
60ms
> 13bit; 8000 punti
2
30ms
> 12bit; 4000 punti
3
15ms
> 11bit; 2000 punti
+4 filtro escluso
(media degli ultimi otto valori campionati)
0.0 ... 20.0 sec
0.0 ... 9.9
punti scala
dP
Formato
0
XXXX
1
XXX.X
2 *
XX.XX
3 *
X.XXX
(*) non disponibile per scale
TC, RTD, PTC, NTC
min...max scala
dell'ingresso
selezionato in t.P
min...max scala
dell'ingresso
selezionato in t.P
-999 ...999
punti scala
d. i. - t. u. - t. d.
0
Nessuna funzione
1
Azzeramento
2
Hold
3
Flash
4
Visualizzazione picco di massima
5
Visualizzazione picco di minima
6
Visualizzazione delta picco
7
Reset memoria di picco
8
Reset memoria di picco + azzer.
9
Reset intercettazioni
10
Reset intercettazioni + picco
11
Reset intercettazioni + azzer.
12
Reset interc. + azzer. + picco
13
Stato uscita OUT1
14
Stato uscita OUT2
15
Stato uscita OUT3
L.S ... H.S
L.S ... H.S