gefran 40T 48 Manuel D'utilisation page 45

Indicateur - détecteur de seuils de température avec entrée universelle
Masquer les pouces Voir aussi pour 40T 48:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 26
Definição das
I n
entradas
Tipo de sonda, sinal
e escala da entrada
principal
Typ TIPO DE
4 DÍGITOS
SONDA
sem ponto dec.
com ponto dec.
Sensor: TC
0
TC J °C
0/1000
0.0/999.9
1
TC J °F
32/1832
32.0/999.9
2
TC K °C
0/1300
0.0/999.9
3
TC K °F
32/2372
32.0/999.9
4
TC R °C
0/1750
0.0/999.9
5
TC R °F
32/3182
32.0/999.9
6
TC S °C
0/1750
0.0/999.9
7
TC S °F
32/3182
32.0/999.9
8
TC T °C
-200/400
-199.9/400.0
9
TC T °F
-328/752
-199.9/752.0
10
TC B °C
44/1800
44.0/999.9
11
TC B °F
111/3272
111.0/999.9
12
TC E °C
-100/750
-100.0/750.0
13
TC E °F
-148/1382
-148.0/999.9
14
TC N °C
0/1300
0.0/999.9
15
TC N °F
32/2372
32.0/999.9
16
TC L °C
0/600
0.0/600.0
17
TC L °F
32/1112
32.0/999.9
18
TC U °C
-200/400
-199.9/400.0
19
TC U °F
-328/752
-199.9/752.0
20
TC G °C
0/2300
0.0/999.9
21
TC G °F
32/4172
32.0/999.9
22
TC D °C
0/2300
0.0/999.9
23
TC D °F
32/4172
32.0/999.9
24
TC C °C
0/2300
0.0/999.9
25
TC C °F
32/4172
32.0/999.9
26
TC °C
Custom
27
TC °F
Custom
Sensor: RTD
28
PT100 °C
-200/600
-199.9/600.0
29
PT100 °F
-328/1112
-199.9/999.9
30 JPT100 °C
-200/600
-199.9/600.0
31 JPT100 °F
-328/1112
-199.9/999.9
Sensor: PTC - NTC
32
PTC °C
-55/120
-55.0/120.0
33
PTC °F
-67/248
-67.0/248.0
34
NTC °C
-10/70
-10.0/70.0
35
NTC °F
14/158
14.0/158.0
Sensor: Tensão + Corr.
36
0...60mV
-1999/9999
-199.9/999.9
37
0...60mV
linear custom
linear custom
38 12...60mV
-1999/9999
-199.9/999.9
39 12...60mV
linear custom
linear custom
40
0...20mA
-1999/9999
-199.9/999.9
41
0...20mA
linear custom
linear custom
42
4...20mA
-1999/9999
-199.9/999.9
43
4...20mA
linear custom
linear custom
44
0...10V
-1999/9999
-199.9/999.9
45
0...10V
linear custom
linear custom
46
2...10V
-1999/9999
-199.9/999.9
47
2...10V
linear custom
linear custom
48
0...5V
-1999/9999
-199.9/999.9
49
0...5V
linear custom
linear custom
50
1...5V
-1999/9999
-199.9/999.9
51
1...5V
linear custom
linear custom
52
0...1V
-1999/9999
-199.9/999.9
53
0...1V
linear custom
linear custom
54 200mV...1V
-1999/9999
-199.9/999.9
55 200mV...1V
linear custom
linear custom
Sensor: Custom PT100 - PTC - NTC
56
PT100
custom
JPT
57
PTC
custom
58
NTC
custom
Se não estiverem disponíveis, os limites mínimo e máximo são postos a 0.
Em caso de linearizações personalizadas (custom), os limites de teste para definir os
erros LO ou HI são dados pelos valores de calibração.
Se estes limites não forem ultrapassados, são considerados como limites os valores
LO_S e HI_S.
Erro máximo de não linearidade para
termopares (Tc),
termorresistência (PT100) e
termistores (PTC, NTC).
O erro é calculado como desvio
em relação ao valor teórico com
referência em % ao valor de fundo
de escala expresso em graus
Celsius (°C).
• Parâmetros das entradas TC / LIN
3 DÍGITOS + marca
(só para o mod. 96)
sem ponto dec.
com ponto dec.
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
0/999
0.0/99.9
32/999
32.0/99.9
-200/400
-99.9/99.9
-328/752
-99.9/99.9
não disp
não disp
não disp
não disp
-100/750
não disp
-148/999
não disp
0/999
não disp
32/999
não disp
0/600
0.0/99.9
32/999
32.0/99.9
-200/400
-99.9/99.9
-328/752
-99.9/99.9
0/999
não disp
32/999
não disp
0/999
não disp
32/999
não disp
0/999
não disp
32/999
não disp
Custom
Custom
Custom
Custom
Custom
Custom
-200/600
-99.9/99.9
-328/999
-99.9/99.9
-200/600
-99.9/99.9
-328/999
-99.9/99.9
-55/120
-55.0/99.9
-67/248
-67.0/99.9
-10/70
-10.0/70.0
14/158
14.0/99.9
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
-999/999
-99.9/99.9
linear custom
linear custom
custom
custom
custom
custom
custom
custom
custom
custom
custom
S, R escala 0...1750°C; erro < 0,2% do fundo de escala (t > 300°C) / para as outras escalas; erro < 0,5% do fundo de escala
T
erro < 0,2% do fundo de escala (t > -150°C)
B
escala 44...1800°C; erro < 0,5% do fundo de escala (t > 300°C) / escala 44,0...999,9; erro < 1% do fundo de escala (t > 300°C)
U
escala -99,9...99,9 e -99...99°C; erro < 0,5% do fundo de escala / para as outras escalas; erro < 0,2% do fundo de escala (t > -150°C)
G
erro < 0,2% do fundo de escala (t > 300°C)
D
erro < 0,2% do fundo de escala (t > 200°C)
C
escala 0...2300; erro < 0,2% do fundo de escala / para as outras escalas; erro < 0,5% do fundo de escala
NTC erro < 0,5% do fundo de escala
Tc tipo J, K, E, N, L
erro < 0,2% do fundo de escala
PT100, JPT100 e PTC
erro < 0,2% do fundo de escala
Seleção dos tempos de
amostragem (resolução).
Somente para entrada
linear
Filtro digital na entrada
principal
Filtro digital na
visualização da variável
de processo
Posição do ponto
decimal para a escala da
entrada principal
Limite mínimo de escala
da entrada principal
e análoga saída
Limite máximo de escala
da entrada principal
e análoga saída
Offset de correção da
entrada principal
Seleção da função
da entrada digital
Seleção da função
da tecla incrementa
ativa só em P.V.
Seleção da função
da tecla decrementa
ativa só em P.V.
Limite inferior de
definição dos limites de
alarme
Limite superior de
definição dos limites de
alarme
45
0
120ms
> 13bit; 8000 pontos
1
60ms
> 13bit; 8000 pontos
2
30ms
> 12bit; 4000 pontos
3
15ms
> 11bit; 2000 pontos
+4 filtro excluído
(média dos últimos oito valores amostrados)
0.0 ... 20.0 seg.
0.0 ... 9.9
pontos de escala
dP
Formato
0
XXXX
1
XXX.X
2 *
XX.XX
3 *
X.XXX
(*) não disponível para as escalas
TC, RTD, PTC, NTC
Mín....máx. da escala
da entrada selecionada
em t.P
Mín....máx. da escala
da entrada selecionada
em t.P
-999 ...999
pontos de escala
d. i. - t. u. - t. d.
0
Nenhuma função
1
Zeramento
2
Hold
3
Flash
4
Visualização do pico de valor máximo
5
Visualização do pico de valor mínimo
6
Visualização do delta pico
7
Reset da memória de pico
8
Reset da memória de pico + zeram.
9
Reset dos alarmes
10
Reset dos alarmes + pico
11
Reset dos alarmes + zeram.
12
Reset dos alarmes + zeram. + pico
13
Estado da saída OUT1
14
Estado da saída OUT2
15
Estado da saída OUT3
L.S ... H.S
L.S ... H.S

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

40t 96

Table des Matières