Using the Digital Display
OUTLET INDICATOR LED DEFINITIONS:
LED Configuration
Standard
1
Alternate
1 This is the default configuration.
Display Options
LED Test
Hold the Mode button for 3 seconds to test the display. For 5 seconds, all LEDs and display
segments will light green, while all Load Indicator LEDs will light yellow. Please visit
www.tripplite.com/support for issues with display segment or Indicator LED functionality.
Viewing the IP Address
i P
i
14-04-275-9332F8.indb 14
LED Color
Outlet Status
Off
Off
Green
On
Yellow
On
Red
Off
Red Flashing
Off
Off
Off
Red
On
Red Flashing
On
Green
Off
Green Flashing
Off
8 8 8
88
At any point, pressing both of the arrow buttons simultaneously for 1/2
second displays the unit's IP address in the 2-digit display.
To Rotating the Display
Description
Outlet power is absent
Circuit breaker is on – Outlet power is present
Outlet's current has exceeded 80% of the outlet
current rating – Outlet power is present
Outlet's voltage is below the Low Voltage threshold –
Outlet power is absent
Circuit breaker has tripped – Outlet power is absent
Outlet power is absent
Circuit breaker is on – Outlet power is present
Outlet's current has exceeded 80% of the outlet
current rating – Outlet power is present
Outlet is disabled – Outlet power is absent
Circuit breaker has tripped – Outlet power is absent
14