6.3 - Programming the limit switches "0" and "1" in SEMI-AUTOMATIC mode
01. Keep the Ascent (or Descent) button pressed to move the shutter until it is half open.
02. Keep the required button pressed and wait for the shutter to stop against the mechanical travel stop. Release the button.
03. Keep the required button pressed and move the shutter to the required position. Release the button. Keep the Ascent and Descent buttons pressed at the same
time for at least 5 seconds and after the motor has made a short downward movement release both buttons.
02
02
6.4 - Adjusting obstacle detection sensitivity
01. Keep the Ascent button pressed until the shutter reaches the travel limit "0" (do not release the button).
02. Then press the Descent button for the same number of times as the level to be selected (press the button for 1 second; wait one second and then press it again).
With the Ascent button still pressed wait for the shutter to make as many movements (downwards) as the number of the new level set. There are 3 levels avail-
able and each one represents the force exercised by the motor when there is an obstacle or in case of impact: level 1 = maximum force / level 2 = medium force
(factory setting) / level 3 = minimum force.
03. Release the Ascent button.
01
6.5 - Total deletion of memory
Caution! - This procedure deletes all data present in the motor's memory, including the positions "0" and "1".
01. Press and hold the two Up and Down buttons simultaneously and wait for the shutter to complete a short movement. Release the Down button.
02. Within 3 seconds of completing the movement, press the Down button 3 times.
03. Release the Up button.
01
5 – English
Caution! • This programming is recommended for shutters with a single mechanical safety stop:
for example, the plugs for limit switch "0" or alternatively the anti-intruder springs on limit switch
"1". • In procedure phase 02 only the limit switch equipped with the mechanical stop must be pro-
grammed, while in phase 03 only the limit switch not equipped with the mechanical stop must be
programmed. The two phases cannot be inverted.
01
03
"0"
01
03
"1"
02
"0"
1
"1"
"0"
x 1 = maximum force /
x 1 = forza massima /
x 2 = medium force /
x 2 = forza media /
x 3 = minimum force /
x 3 = forza minima /
02
03
x 3
1
5
sec.
1
5
sec.
03
1 /
?
2 /
3 /