ANALOGUE INPUTS
N
B1 P.A.
B2 P.B.
B3 TIA (TUAC)
B4 TGP
B5 TUA
B6 TAE SUWH
B7 SUR
B8 TEV
B9 TAE SUWH
B10 TL SIWH
B1 EXP SIR SFC
B2 EXP SUR SFC2
B3 EXP SRU
B4 EXP
28
Air / water units type 00 / 01
Circuit high pressure transducers
Low pressure circuit transducer
Temperature probe inlet water
(MASTER) Evaporator common
outlet water temperature probe
(SLAVE !)
Compressor discharge tempera-
ture probe
Output water temperature probe
Daikin Modulating capacity
control: Outside air temperature
probe
Bitzer e Daikin Step cap. control:
Amperometric transformer input
Master: multifunctional input
Slave: Recovery outlet tempera-
ture probe
Evaporator gas temperature
probe
Daikin Modulating capacity con-
trol: Compressor potentiometer
Bitzer e Daikin Step cap. control:
Outside air temperature probe
Liquid temperature probe
Recovery inlet temperature
probe Inlet probe Free-cooling
coil inlet probe (Glycol free)
Recovery outlet temperature
probe Free-cooling coil outlet
probe (Glycol free)
Intermediate exchanger water
inlet probe (Glycol free)
Not used
Water / water units type 03
/ 04
Circuit high pressure transducers
Low pressure circuit transducer
Temperature probe inlet
water (MASTER) Evaporator
common outlet water tem-
perature probe (SLAVE !)
Compressor discharge tem-
perature probe
Evaporator outlet water
temperature probe
Daikin Modulating capacity
control Condenser outlet
water temperature probe
Bitzer e Daikin Step cap. control:
Amperometric transformer
input
Master: multifunctional input
Slave: Recovery outlet tem-
perature probe
Evaporator gas temperature
probe
Daikin Modulating capacity
control Compressor poten-
tiometer
Bitzer e Daikin Step cap.
control: Condenser output
water temperature probe
Condenser inlet water tem-
perature probe (MASTER)
Condenser common outlet
water temperature probe
(SLAVE !)
-
Free-cooling coil outlet
probe (Glycol free)
Intermediate exchanger wa-
ter inlet probe (Glycol free)
Not used
WF-WSA-WSB-WSH UNITS
NOTES
Probe type 4-20 mA
Range 0-30 bar
Probe type 4-20 mA
Range 0-10 bar
Probe type NTC 10k Carel -
Only on master -
(Only on Slave1)
Probe PT1000
Probe type NTC 10k
Probe type NTC 10k In case of
use as transformer input do not
enable analogue input B6
Probe type NTC 10k In case of
use as multifunctional input do
not enable analogue input B7
Probe type NTC 10k
Probe type NTC 10k In case of
use as potentiometer do not
enable analogue input B9
Probe type NTC 10k
Probe type NTC 10k
On expansion
Probe type NTC 10k
on expansion
Probe type NTC 10k
On expansion
Probe type NTC 10k
On expansion