Installation Instructions
G.
Continued.
H.
External Static Pressure Setting
Using Wired Controller
Wired controller- QACT17A settings
1. After backlight is lit at the wired controller off, press
and hold FAN and TEMP + button for 10 seconds.
2. The static pressure selection will appear in the
upper right hand corner.
3. The parameter value of ESP grades can be
adjusted by pressing TEMP+ or TEMP- buttons.
4. Press FAN button to confirm the change.
ESP Level (ESP grade)
1
2
3
4
5
6
7
8
9
10
Use the Up and Down Arrow buttons to adjust the
static pressure level numbers. Then press the Set
button to confirm.
10
Step 2 - Mounting the Unit (Cont.)
0.10 in WC.
0.15 in WC.
0.20 in WC.
0.28 in WC.
0.36 in WC.
0.40 in WC.
0.44 in WC.
0.48 in WC.
0.52 in WC.
0.60 in WC.
I.

DIP Switch Settings

After attaching the 14/4 stranded copper wire to the terminal
block, the DIP switch bank on the PCB need to be checked.
Need to make sure all switches are in the correct position
including a field-supplied external static pressure setting per
the table below.
SW3_1 Special fresh
[1]
Air (Canada
particular Area)
SW3_2 Reserved
[2]
SW3_3 Auxiliary
[3]
heater
SW3_4 Slim duct or
[4]
MESP DUCT
[5]
OFF OFF
OFF OFF
OFF OFF
OFF OFF
SW3_5
IDU address
OFF ON
SW3_6
for wired
OFF ON
SW3_7
controller
OFF ON
SW3_8
group
OFF ON
Control
ON
application
ON
ON
ON
ON
ON
ON
ON
[1]
OFF OFF
ON
SW1_1
OFF ON
SW1_2
Capacity
ON
SW1_3
OFF OFF
ON
OFF ON
ON
SW1_4 Room card
OFF
ON
SW1_5 Heat pump /
OFF
Cool only
ON
SW1_6 Fresh air/E.A.O OFF
ON
SW1_7 Filter change
OFF
caution
ON
SW1_8 North America/
OFF
NON- North
America
ON
ON
Special Fresh
Factory default
Air function
setting: OFF
valid
OFF
Special fresh
Air funtion
invalid
ON
Reserved
Factory default
OFF
Reserved
setting: OFF
ON
Auxiliary
Factory default
heater
setting: OFF
Function valid
OFF
Auxiliary
heater
Function
invalid
ON
MESP DUCT
Factory default
(10 ESP level)
setting: According
to model
OFF
Slim DUCT (10
ESP level)
[6]
[7]
[8]
IDU Address
OFF
OFF
0# (main)
(Factory default
setting)
OFF
ON
1# (subordinate)
ON
OFF
2# (subordinate)
ON
ON
3# (subordinate)
OFF
OFF
4# (subordinate)
OFF
ON
5# (subordinate)
ON
OFF
6# (subordinate)
ON
ON
7# (subordinate)
OFF
OFF
OFF
8# (subordinate)
OFF
OFF
ON
9# (subordinate)
OFF
ON
OFF
10# (subordinate)
OFF
ON
ON
11# (subordinate)
ON
OFF
OFF
12# (subordinate)
ON
OFF
ON
13# (subordinate)
ON
ON
OFF
14# (subordinate)
ON
ON
ON
15# (subordinate)
[2]
[3]
Capacity
OFF
9000BTU/h
OFF
OFF
12000BTU/h
OFF
18000BTU/h
ON
OFF
24000BTU/h
ON
Reserved
OFF
ON
Reserved
ON
Reserved
ON
ON
Reserved
Room card invalid (factory
default)
Room card valid
Heat pump (factory
default)
Cool only
Fresh air valid (factory
default)
External alarm output valid
Without filter change
caution (factory default)
With filter change caution
North America area (USA
& Canada) (factory default)
NON-North America
31-5000493 Rev. 1