LL TP HCS
Factory settings
- switch-off delay (dip switch): 6 min
- switch-on delay (dip switch): 45 seconds
- humidity threshold: 70 %RH
- operation mode: Timer
- 2 speeds: position A of the jumper (fig.16)
Possible settings
- Jumper setting (fig 15b,16). The motor has two operating speeds: V1 and V2. By appropriately setting the
jumpers as described in the following table A it is possible to determine which will be the maximum and
minimum speed between V1 and V2. The timer will always act on V1.
- Dip-switch settings (fig. 17). N.B. Before making any changes to the dip-switches, disconnect the electric
power supply. It is possible to configure the time lag for switching on/off, and the Relative Humidity threshold
value (see under Use), by appropriately setting the 6 dip-switches as described in the following tables:
0 sec.
T
A
45 sec.
6 min.
12 min.
T
B
18 min.
24 min.
70%
90%
U
R
80%
60%
Timer
Operat.
mode
Disabl. HCS
T
A
T
= time lag for switching on
B
T
= time lag for switching off
C
U
= automatic cycle time
R
= relative humidity
Int. 1
Int. 2
OFF
--
ON
--
--
OFF
--
OFF
--
ON
--
ON
--
--
--
--
--
--
--
--
--
--
--
--
DIP switch
Int. 3
Int. 4
--
--
--
--
OFF
--
ON
--
OFF
--
ON
--
--
OFF
--
OFF
--
ON
--
ON
--
--
--
--
Int. 5
Int. 6
--
--
--
--
--
--
--
--
--
--
--
--
OFF
--
ON
--
OFF
--
ON
--
--
OFF
--
ON