X82.3
Labelling
GCL
GI2
I2B
I2A
GCL
GI1
I1B
I1A
AIS
X82.4
Labelling
GCL
GI4
I4B
I4A
GCL
GI3
I3B
I3A
AIS
Cable cross−sections and tightening torques
Type
Wire end ferrule,
insulated
Rigid
Stripping length or contact length: 9 mm
Insulated wire end ferrules according to DIN 46228, part 4, 0.5 mm
L1 = 10 mm can be used.
EDK94AYAF DE/EN/FR/ES/IT 1.0
Description
GND clock output
GND SD−In2
Sensor input SD−In2, channel B
Sensor input SD−In2, channel A
GND clock output
GND SD−In1
Sensor input SD−In1, channel B
Sensor input SD−In1, channel A
Restart acknowledgement input ("Acknowledge In Stop", 1−channel,
bridged to X82.4/AIS)
Description
GND clock output
GND SD−In4
Sensor input SD−In4, channel B
Sensor input SD−In4, channel A
GND clock output
GND SD−In3
Sensor input SD−In3, channel B
Sensor input SD−In3, channel A
Restart acknowledgement input ("Acknowledge In Stop", 1−channel,
bridged to X82.3/AIS)
2
[mm
]
0.25 ... 0.75
Spring terminal
0.14 ... 1.5
l
Electrical installation
[Nm]
AWG
24 ... 18
26 ... 16
[lb−in]
Spring terminal
2
2
or 0.75 mm
− length