1.1. GENERAL
AmpFlex
sensors take the form of a flexible coil connected by a shielded lead to a housing containing
®
the signal processing electronics, powered by batteries.
The flexibility of the sensors facilitates the clamping of the conductor to be measured, whatever its nature
(cable, bar, strand, etc.) and its accessibility. The design of the coil opening and closing device, by snap
locking, allows handling while wearing protective gloves.
The electronic unit can be connected to the mV
impedance of ≥ 1 MW.
1.2. SINGLE-PHASE AMPFLEX
AmpFlex
series A110 single‑phase sensors constitute a line of three models, 45, 80, and 120 cm long,
®
that convert alternating currents ranging from 3 to 3000 A (for the 45 and 80 cm models) or from 30 to
30,000 A (for the 120 cm model) into proportional AC voltages.
Flexible coil.
Sensor opening device.
Shielded cord.
Switch to activate the
instrument and choose
the sensitivity.
Auto Power Off button
to deactivate automatic
switching off.
Type B Micro-USB port
to connect a 5V power
supply.
1. PRESENTATION
or V
ac
ac
®
3 A
30 A
300 A
3000 A
OFF
P
Auto Power Off
3 A
: 1000 mV
/ A
30 A
: 100 mV
/ A
300 A
: 10 mV
/ A
3000 A
: 1 mV
/ A
AC CURRENT PROBE
600 V CAT IV
1000 V CAT III
26
input of a measuring instrument having an input
2 banana plugs, dia. 4 mm.
Red OL indicator reporting an
overshoot of the measurement
range (overload).
Orange Auto Power off
i n d i c a t o r i n d i c a t i n g t h a t
automatic standby switching
of the device is activated.
Green On indicator indicating
that the device is on (blinking)
OL
or connected to the optional
On
mains adapter (steady).
A 110
Connecting cord between the
electronic unit and a display
device.