5. Maintenance
Mounting the new battery module
Carry out the above instructions in reverse order.
To ensure safety and high performance, use only batteries supplied by EATON.
Take care to firmly press together the two parts of the connector during remounting.
5.3 Maintenance on a UPS equipped with the HotSwap MBP module
HotSwap MBP
34007776EN/AD - Page 20
D
E
7
49
50
51 52
8
9
10
44
53
54
55
56
31
D - Remove the metal protection cover in
front of the battery (two screws).
E - Pull the plastic tab to remove the
battery block and replace it.
The HotSwap MBP module makes it
possible to service or even replace the
UPS without affecting the connected loads
(HotSwap function).
Maintenance:
1 - Set switch (53) to the Bypass position.
The red LED on the HotSwap MBP module
goes ON, indicating that the load is
supplied directly with AC input power.
2 - Stop the UPS by pressing the ON/OFF
button (27) on the UPS control panel. LED
(51) "UPS ON - OK to switch" goes OFF, the
UPS can now be disconnected and
replaced.
Return to normal operation:
1 - Check that the UPS is correctly
connected to the HotSwap MBP module.
2 - Start the UPS by pressing the ON/OFF
button (27) on the UPS control panel. LED
(51) "UPS ON - OK to switch" on the
HotSwap MBP module goes ON
(otherwise, there is a connection error
between the HotSwap MBP module and
the UPS).
3 - Set switch (53) to the Normal position.
The red LED on the HotSwap MBP module
goes OFF.