Output personalisation
Function
Output voltage
Frequency converter
Output frequency
Transfer to the bypass
AC input
Overload level
(1) These parameters may be modified only when the UPS is OFF.
Detailed comments are available in the Personal Solution-Pac software.
ON/OFF personalisation
Function
Cold start
Automatic restart
Energy savings
Detection of phase/
neutral inversion (SWF)
Battery personalisation
Function
Battery test
Selection of the backup
time
Battery protection
against deep discharge
4.4 Personalisation using external software
Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the
Personal Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.
4. Access to measurements and personalisation data
Factory setting
(1)
230 Volts AC
(1)
Disabled
(1)
Automatic selection
Bypass AC power must
(1)
be within tolerances
(1)
102%
Factory setting
Enabled
Enabled
Disabled
Disabled
Factory setting
Weekly test
Automatic detection of
number of battery
modules
Enabled
Other available settings
Comments
200/208/220/240 Volts AC
Enabled
The connected devices are never
transferred to the bypass.
50 or 60 Hz
User selectable only if the
frequency-converter function is
enabled.
Bypass AC power may be
outside tolerances
50 / 70%
Alarm if threshold is overrun.
Other available settings
Comments
Disabled
Disabled
The UPS restarts automatically
when AC input power returns.
Enabled
When function enabled, battery
shuts down when power drops to
<5%.
Enabled
When function enabled, the UPS
remains OFF if the system detects
phase/neutral inversion.
Other available settings
Comments
No test / daily test /
monthly test
65 to 400 Ah
Disabled
When function disabled, EATON
warranty no longer applies.
- Page 17
34007776EN/AD