Service menu
No. Description
Signalling of switching output
Signalises the control of switching outputs by a
090
flashing heating resp. cooling symbol.
Control direction switching output
Sets the control direction of connected actua-
110
tors:
• Normally closed (NC)
• Normally open (NO)
Antifreeze temperature
Activates the antifreeze protection function
161
DEU
when the temperature falls below the set tem-
perature.
ENG
ENG
Smart Start/Smart Stop function
(only Control)
170
FRA
Teaches the temperature behaviour of the room.
NDL
Valve protection function
190
Cyclic opening of the valve in order to avoid
ITA
clogging.
Valve activation duration
ESP
191
Time for triggering actuators for performing the
valve protection function.
44
Setting
0 = deactivated
1 = activated
Standard: 1
0 = NC
1 = NO
Standard: 0
5 ... 10 °C
Standard: 5
0 = deactivated
1 = activated
Standard 1
0 ... 28 days
Standard: 14
0 ... 10 minutes
Standard: 5 min