Sterilization is performed circularly by the d value. Once the circular sterilization
conditions are met, sterilization is performed regardless of on/off status of the controller
and beyond limit of common modes and functions except VACATION. However, users
can stop sterilization under process by pressing the ON/OFF button to shut it down.
(But it can only stop sterilization for this time without affecting circular sterilization, the
preset circular sterilization function still works.)
OFF reminder for sterilization failure:
If the OFF icon is displayed at the clock position after the STERILIZATION function
is started, sterilization fails and the water temperature required for sterilization cannot
be reached. The OFF reminder can be canceled when any button is pressed.
The OFF reminder only indicates that sterilization fails for this time without
affecting circular sterilization.
The OFF reminder is shown in the following figure.
Note:
① When time goes from 23:59 to 00:00, the system enters a new day, which is the
basis for increasing the number of days.
② Every time after the STERILIZE function is started or sterilization parameters
are adjusted in the sterilize function setting interface, sterilization will be
performed for once immediately and the day interval for sterilization will be
recalculated accumulatively. Even when sterilization is being performed,
operations such as sterilize function resetting and day interval adjusting for
sterilization will also cause recalculation of the day interval.
Controller For The Air Source Heat Pump Water Heater