Specifications and Accuracy
GT-55e and GT-85e
Operating and Storage Conditions:
Temperature: –10 °C to 55 °C
Humidity: 0% to 85% relative humidity
Altitude: 2000 m maximum
Pollution Degree: 2
Indoor use only.
Remove batteries before storing. Store in dry and
closed area. If tool is transported in extreme
temperatures, a recovery time of at least 2 hours is
required before operation.
Measurement Categories: CAT III 1000 V; CAT IV 600 V
Type of Protection: IP64
CE:
EN61326 :
EN55011 :
Safety:
EN61010-1 : 2001
EN61010-031 : 2002
EN61243-3 : 1998
EN61243-3/CI : 2000
EN60529 : 1992/AI2000
GS38
Functionality:
EN61243-3 : 1998
EN61557-7 : 1997
EN61557-10 : 2001
EN61557-1 : 1997
GT-55e
Voltage Range: 6 V to 690 V AC/DC
Bargraph Resolution: ± 6, 12, 24, 36, 50, 120, 240, 400,
690 V
Voltage Detection: Automatic
Acoustic Signal Sound:
AC Voltage: Yes
– DC Voltage: Yes
Polarity Detection: Full range
Range Detection: Automatic
Response Time: < 0.1 s
Frequency Range, DC: 45 Hz to 65 Hz
Automatic Load (RCD): Yes
Peak Current: Is < 0.2 A / Is (5 s) < 3.5 mA
Operation Time: ED (DT) = 30 s
Recovery Time: 10 min
Auto Power On: < 12 VAC/DC
Power Supply: 2 x 1.5 V Micro IEC LR03
Power Consumption: Max. 30 mA / approx. 250 MΩ
Single-pole Voltage Detection Test
Voltage Range: 100 V to 690 V AC
Frequency Range: 45 Hz to 65 Hz
Continuity Test
Threshold: < 200 kΩ
Test Current: < 20 µA
Overvoltage Protection: 690 V AC/DC
GT-55e • GT-85e
13