CAUTION:
Improperly adjusted manual bypass valves will result in damage to the heater if the flow rates are not
maintained under all operating conditions as specified in listed SPECIFICATION. The heat exchanger will fail and this damage
will not be covered under the manufacturer's warranty.
CAUTION:
The heat pump must be protected from back siphoning of water. If there is any chance of back siphoning,
provide a check valve between the pool and the filter pump inlet. Failure to follow the instructions may result in property damage
due to flooding.
CAUTION:
Automatic erosion type chlorinators, if used, must be installed downstream (between the heat pump and the
pool) of the heat pump, and a check valve (or Hartford Loop) installed in a manner that will not allow the raw chlorine to drain
back to the heat pump when the water pump is off. Failure to follow the instructions may result in property damage.
CAUTION:
Do not pour chemicals directly into the skimmer. It could result in damage to your system and heat pump.
Arrangement of pool system components other than as illustrated in figure5 can affect the operation of the heat pump's water
pressure switch. Location of the heat pump above or below the elevation of the pool water surface can also affect operation of the
switch. In general, the pressure switch can be adjusted to accommodate this effect if the heat pump water connections are no more
than six (6) feet [1,8 m] below the pool water surface or no more than fifteen (15) feet [4,6 m] above it. See instructions for pressure
switch adjustment in the START-UP section of this manual. If the heat pump is installed outside of this range, an external pressure
switch may need to be installed in the plumbing upstream of the heat pump.
NOTICE:
Be advised, that when pool equipment is located below the pool surface, a leak at this lower level can result in
large-scale water loss or flooding. Manufacturer is not responsible for water loss or damage it causes
.
CONNECTIONS:
The heater is equipped with
detachable connectors for water. These fittings
must be installed on the heat pump water inlet and
outlet to facilitate servicing and winterizing the unit.
(See figure6). Heat sinks, heat tapes, firemen
switches, and check valves are not required on the
heater. However, if there is any chance of "back-
siphoning" of outlet water when the pump stops
running, it is suggested that a check valve and
chemical loop be used on the heater outlet pipe
down stream of bypass system.
Figure5: Pad Plumbing Layout
Figure6: In Ground Included Connectors
USE ONLY GENUINE REPLACEMENT PARTS
51300002101 RevA
11