Do not install where water may run-off a roof into the heater. A gutter may be needed to protect the heater.
CAUTION:
Make sure the heat pump is not located where large amounts of water may run-off from the roof into the unit.
Sharp sloping roofs without gutters will allow massive amounts of rainwater, mixed with debris from the roof to be forced
through the unit. Failure to follow the instructions may result in property damage and a voided warranty.
1. See table3 and figure3 for clearances.
2. If the heat pump is to be installed below a vertical
overhang such as shown in figure3, the unit must have a
minimum of 72in. [1.8m] of clearance from the top of the
heat pump to the bottom of the cover or overhang.
3. Install the heat pump a minimum of 60in. [1.5m] from the
inside wall of the pool, spa, solid fence, or permanent
barrier. Canadian installations require a minimum of 120
in. [3 m] of clearance from pool water.
24in
36in

EQUIPMENT PAD

: Place the heat pump on a level surface such as concrete or a fabricated slab (pad). This allows proper
drainage of condensation and rainwater from the base of the unit. If possible, the pad should be placed at the same level or slightly
higher than the filter system equipment pad.
FLOORING
: This heater may be installed on either non-combustible flooring or combustible flooring that does not reduce the
bottom clearance of the heater. Ultralite™ or equivalent concrete-over-foam HVAC pads are acceptable.
DRAINAGE AND CONDENSATION
and drain at a steady rate, usually three to five gallons per hour, depending upon ambient air temperature and humidity. The more
humid the conditions, the more condensation will be produced. Use the supplied condensate drain to route the condensate away
from the unit and dispose appropriately. It is easy to mistake the condensation for a water leak inside the unit. A way to verify that
the water is condensation is to shut off the unit and keep the pool pump running. If the water stops running out of the base pan, it is
condensation collecting around the unit. A quicker way is to check the water for CHLORINE. If there is no chlorine present in the
water around the unit, then it's condensation.
Figure3: Outdoor Minimum Clearances
24in
24in
: Condensation will be produced by the evaporator coil when the unit is heating water
USE ONLY GENUINE REPLACEMENT PARTS
Table3: Installation Required Clearances
Heat Pump Panel
Top
Front (control)
Rest of Perimeter
Free
from
run off
36in
51300002101 RevA
(in.)
Outdoor Clearance
Unobstructed
24-36
24
24in
9