Installation Verification Test

SER 6004, SER 9504, SER 13004 Models
Without external control
1. Fan speed selector switch
• Set fan Speed selector switch to Standby.
2. Start-up
• Apply power to unit
• Unit should enter Exhaust only defrost mode for a 30 second duration and the following should occur:
Exhaust fan runs in HIGH speed
Supply fan remains off
3. Standby
• Following the start-up unit should enter Standby mode. The following should occur:
Exhaust fan shuts off
Supply fan remains off
4. LOW speed
• Set fans speed selector switch LOW speed. The following should occur.
Exhaust fan runs in LOW speed
Supply fan runs in LOW speed
5. Medium speed
• Set fans speed selector switch MED speed. The following should occur.
Exhaust fan ramps up to MED speed
Supply fan ramps up to MED speed
6. Test completion
Set fan speed selector switch to desired setting
Installation Verification test is complete
With external control
1. Start-up
• Apply power to unit
• Unit should enter Exhaust only defrost mode for a 30 second duration and the following should occur:
Exhaust fan runs in HIGH speed
Supply fan remains off
2.
• Following start-up unit will respond to external control
• Consult user manual/instruction provided with external controller and ensure unit responds appropriately.
3. Test completion
• Installation Verification test is complete