Modes of operation

1. Continuous / Ventilation Mode
In this mode of operation both fans are operating and exchanging inside air for outside air. The energy recovery ventilator (ERV) will operate at the selected
rate, either at low or medium speed, and switches to high speed when activated by an optional remote control. The "Low" and "Med" fan speed selection
will cause the unit to operate in continuous ventilation mode at a reduced exchange rate. Continuous mode is recommended, since pollutants are slowly
but constantly being generated in a building.
2. Intermittent / Standby Mode
The system is always on standby and operates at high speed when activated by an optional remote control (required): "Standby" should be selected if
the user wishes to stop the unit from continuous exchange.
3. Defrost by evacuation
A preset defrost sequence is activated at an outdoor air temperature of 23°F (5°C) and lower.
During the defrost sequence, the supply blower shuts down & the exhaust blower continues to ventilate for a preset time. The unit then returns to
the normal operation, and continues the cycle.

Setting speed

The ERV is shipped from the factory on low speed, intermittent operation can be obtained by toggling switch located on outside of cabinet. External
low voltage contacts allow for high speed operation when optional remote control is used.