SHR / VHR Series
Heat recovery ventilators
SHR 1504 • SHR 1505R • SHR 2004 • SHR 2005R • SHR 3005R • SHR 3205RD
Your ventilation system should be installed in conformance with the appropriate provincial requirements or, in the absence of
such requirements, with the current edition of the National Building Code, and / or ASHRAE's "Good Engineering Practices".
United States
10048 Industrial Blvd., Lenexa, KS, 66215
Tel.: 800.747.1762 • Fax: 800.487.9915
Canada
50 Kanalflakt Way, Bouctouche, NB, E4S 3M5
Tel.: 800.565.3548 • Fax: 877.747.8116
Fantech reserves the right to modify, at any time and without notice, any or all of its products' features, designs,
components and specifications to maintain their technological leadership position.
Please visit our website www.fantech.net for more detailed technical information.
Installation Manual
VHR 1404 • VHR 1405R • VHR 2004 • VHR 2005R
Item #: 405190
Rev Date: 062413
fantech

Publicité

Chapitres

Table des Matières
loading

Sommaire des Matières pour Fantech SHR Serie

  • Page 1 Tel.: 800.565.3548 • Fax: 877.747.8116 fantech Fantech reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position. Please visit our website www.fantech.net for more detailed technical information.
  • Page 2 Your ventilation system should be installed in accordance with the local building code that is in effect, in absence of such requirements, it is recommenced to check with local authorities having jurisdiction in your area prior to installing this product fantech...
  • Page 3: Table Des Matières

    MAINTENANCE CHART ............... 18 fantech...
  • Page 4: Determining Your Airflow Requirement

    * ASHRAE 62.2-2010 Table 4.1, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings. Bathroom: If the HRV is going to provide the required local exhaust ventilation for each bathroom with each a continuous 20 CFM (10 L/s), this ventilation rate can be considered as part of the whole-building ventilation rate. fantech...
  • Page 5: Installation Examples

    HRV's airflow must be balanced on site, using the procedure found in section “AIRFLOW BALANCING”. FEL 4 (4” Miter Elbow) Exhaust CG 4 (4” Adjustable Grill) Bathroom Bedrooms Central Control - optional Fresh air to living room Fresh Air 460 mm Exhaust Air fantech...
  • Page 6: Partially Dedicated System

    1 m (3' 3") Stale air coming from different areas of the min. house (i.e. bathroom, kitchen). recommended Cold air return * Unit air flow should be balanced while HRV is on "High" speed and fur- nace blower is running. fantech...
  • Page 7: Simplified Installation - Option 1

    1 m (3' 3") Outside Stale air coming from different areas of the min. house (i.e. bathroom, kitchen). recommended Cold air return * Unit air flow should be balanced while HRV is on "High" speed and fur- nace blower is running. fantech...
  • Page 8: Simplified Installation - Option 2

    1 m (3' 3") Outside Stale air coming from different areas of the min. house (i.e. bathroom, kitchen). recommended Cold air return * Unit air flow should be balanced while HRV is on "High" speed and fur- nace blower is running. fantech...
  • Page 9: Exterior Ducting Installation

    Pull the insulation procedure for both the supply insulated flexible duct. Cut a over the duct and pull the vapor and exhaust hoods. hole for both the intake and barrier over the sleeve. Secure exhaust hoods. with appropriate tape or sealant. fantech...
  • Page 10: Interior Ducting Installation

    As per building codes and installation requirements for combustion appliances: Air return ducts, or openings for air return, should not be placed in enclosed spaces containing combustion appliances that are subject to spillage. fantech...
  • Page 11: Hrv Installation

    The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing point. A “P” trap should be made in the drain line. This will prevent odors from being drawn back up into the unit. 2 Install the drain hose, 1 Install the drain nipple. making a “P” trap fantech...
  • Page 12: Start Up Procedure

    • For optimal performance, HRV unit should be re-balanced after a major renovation or after the installation of extra grilles or registers. fantech...
  • Page 13: Adjusting Airflow

    Reading should also be taken at a minimum here distance of 457 mm (18") from the unit or Measure elbow. Measurement should also be made here Minimum prior to any transition in the duct work so 457mm (18") entire airflow is measured. fantech...
  • Page 14: Low Voltage Control

    Recirculation mode is only available on models with the "R" suffix at the end of the model number. • Dehumidifier controls will only work if outdoor humidity levels are lower than indoor humidity levels. Never use the Dehumidistat controls when outdoor temperatures are above 15 C (59F). fantech...
  • Page 15: Electrical Connections

    Electrical connections fantech...
  • Page 16 WIRE JOINT FURNACE 24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE Never connect a 120 volt AC circuit to the terminals of the Accessory Control Contacts. Only use the low voltage class 2 circuit of the furnace blower control. fantech...
  • Page 17: Troubleshooting

    Everything is in good operations LED is not flashing No Power is being transmitted to the Control Board Make sure unit is plugged. Transformer may need replacing. Note: It is best to get the unit checked by a certified HVAC Contractor/Technician. fantech...
  • Page 18: Maintenance Chart

    Lines beginning of the warranty period. Vacuum the Inside of the Annually • The fans found in all Fantech HRVs Unit require no lubrication, and are factory balanced to prevent vibration and Clean and Unblock Annually promote silent operation.
  • Page 19 NOTES fantech...
  • Page 20 NOTES fantech...
  • Page 21: Ventilateurs Récupérateur De Chaleur

    Tél.: 800.565.3548 • Fax: 877.747.8116 fantech Fantech se réserve le droit de modifier partiellement ou entièrement, en tout moment et sans préavis, les caractéristiques, la conception, les composants et les spécifications de ses produits, afin de conserver sa position de leader de technologie.
  • Page 22: Information Conseil Technique Pratique

    Votre système de ventilation doit être installé en conformité avec le code du bâtiment local qui est en vigueur, en l’absence de telles exigences, il est recommandé de vérifier auprès des autorités locales ayant juridiction dans votre région avant d’installer ce produit. fantech...
  • Page 23 TABLEAU D'ENTRETIEN ............... 38 fantech...
  • Page 24: Déterminez Vos Besoins De Ventilation

    Salle de bain: Si le VRC fournit la ventilation d’échappement locale requise pour chaque salle de bain avec chacun un 20 PCM continue (10L/s), ce taux de ventilation peut être considéré comme faisant partie du débit de ventilation de tout le bâtiment. fantech...
  • Page 25: Exemples D'installation

    FEL 4 (Coude 4 po) Grille d'évacuation CG4 (Grille ajustable 4 po) Salle de bains Bedrooms Commande centrale (en option) Air frais acheminé au salon Approvisionnement Évacuation Air frais 460 mm Air évacué fantech...
  • Page 26: Système Partiellement Spécialisé

    (au besoin), po) min. cuisine (au besoin). recommandé Retour d'air frais * L’appareil est généralement équilibré à haute vitesse et pendant que le Fournaise à ventilateur de la fournaise est en marche. air pulsé fantech...
  • Page 27: Conduits Vrc/Fournaise Pour Installation Simplifiée - Option

    Air vicié provenant de différents endroits 3po) min. de la maison recommandé (salle de bains, cuisine). Retour d'air frais * L’appareil est généralement équilibré à haute vitesse et pendant que Fournaise à ventilateur de la fournaise est en marche. air pulsé fantech...
  • Page 28: Installation Simplifiée - Option 2

    3 po) min. de la maison 3 po) min. recommandé recommandé (salle de bains, cuisine). retrour d'air frais * L’appareil est généralement équilibré à haute vitesse et pendant que le Fournaise à ventilateur de la fournaise est en marche. air pulsé fantech...
  • Page 29: Installation Des Conduits Extérieur

    Percez un trou pour la Fixez à l’aide de ruban adhésif hotte d’aspiration et un trou en toile. pour la hotte d'échappement fantech...
  • Page 30: Installation Des Conduits Intérieur

    Selon les codes du bâtiment et les codes d’installation des appareils de combustion, il est interdit de poser des grilles de reprise d’air ou de percer une ouverture pour une prise d’air dans une pièce close où se trouvent des appareils à combustion sujets à des déversements. fantech...
  • Page 31: Installation

    Faites un siphon en P dans le tuyau d'écoulement. Ce siphon empêche le retour des odeurs vers l’appareil. 2 Installer le tuyau 1 Posez l'embout de drain d'écoulement et faite une boucle (siphon en P). fantech...
  • Page 32: Procédure De Démarrage

    Afin d'assurer une performance optimale, le VRC devrait être rééquilibré après toute rénovation majeure ou après l'ajout de nouveau conduits. fantech...
  • Page 33: Équilibrage Du Débit D'air (Suite)

    457mm (18po) (18 po) de l’appareil ou d’un coude et avant toute connexion avec un autre conduit. Les Mesurez mesures devraient être prises avant toute Minimum transition dans les conduits, afin de 457mm (18po) mesurer le débit entier de l'air. fantech...
  • Page 34: Système De Contrôle À Basse Tension

    • Le mode recirculation est seulement offert sur les modèles ayant le suffixe "R" à la fin du numéro de modèle. • Les contrôles du déshumidificateur fonctionneront seulement si le niveau d'humidité extérieur est inférieur au niveau d'humidité intérieur. Ne jamais utiliser les contrôles de déshumidificateur lorsque la température extérieur est plus élevée que 15 C (59 F). fantech...
  • Page 35: Schémas Électrique

    Schémas électriques fantech...
  • Page 36: Schémas Électroniques

    COOLING SYSTEM SYSTÈME DE DEUx FILS WIRE REFROIDISSEMENT Ne raccordez jamais un courant alternatif de 120V aux bornes de synchronisation de la fournaise. N'utilisez que le conduit basse tension de classe 2 de la commande du ventilateur de la fournaise. fantech...
  • Page 37: Dépannage

    DEL ne clignote pas – La plaquette électronique n'est pas alimentée – S'assurer que la plaquette est branchée – Remplacer le transformateur si nécessaire. Note: Il est toujours recommandé de faire vérifier l'appareil par un Contracteur/Technicien certifié en CVC fantech...
  • Page 38: Tableau D'entretien

    à proximité du domicile de l'acheteur ou dans sa région. • Fantech se réserve le droit de fournir des pièces remises à neuf comme pièces de rechange. • Les frais de transport, de retrait et d'installation sont assumés par...
  • Page 39 Notes fantech...
  • Page 40 Fantech reserves the right to make technical changes. Fantech se réserve le droit de faire des changements tech- For updated documentation please refer to www.fantech.net niques. Pour de la documentation à jour, s'il vous plaît se référer au www.fantech.net Fantech®...