LEGRAND DMX3 Mode D'emploi page 98

Masquer les pouces Voir aussi pour DMX3:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DMX
Manual control
Draw-out cell
Motor operator
Aux contacts and alarms
Insert/draw-out contacts
Shunt trip coil
Closing coil
UVR coil
Key lock/pad lock
Cable interlock
98
3
Objet
Check
To perform at least two opening/
closing cicles
discharged
discharged
charged
charged
discharged
discharged
discharged
discharged
To perform at least one cycle
insert/test/draw out postion
Supply the motor operator
and perform at least 2 cycles
opening/closing . The motor
operator must load the springs after
each opening/closing event and
stop when the springs are ready
Verify the correct signals
Verify the correct signals
Close the breaker . Charge the
spring, supply the coil and verify
the tripping
Open the breaker . Charge the
spring, supply the coil and verify
the closing
Cut the UVR power and check the
breaker tripping .
Verify that it's impossibile
to close the breaker without UVR
power .
Verify the proper functioning
Adjust and verify
the proper functioning
Remark