According to IEC60947-3
Number of poles
Rating In (A)
Rated insulation voltage Ui (v)
Rated impulsive voltage Uimp (kV)
Rated operational voltage (50/60Hz) Ue (V)
Rated short-circuit
making capacity
Icm (kA)
Rated short-circuit
withstand current
Icw (kA)
Suitability for insulation
Mechanical
endurance (cycles)
Electrical endurance (cycles)
Opening time
Closing time
Visualization of contacts position
Visualization of charged/discharged springs
Auxiliary contacts
Shunt trip
Closing coil
Undervoltage release
Undervoltage release with time delay
Motor operator
Mechanical counter
* Standard version with n° 4 NO/NC (max n° 6 option contacts 0 281 75) .
S=Standard
O=Optional
SWITCH DISCONNECTORS
230V~
415V~
500V~
600V~
690V~
230V~ (t=1s)
415V~ (t=1s)
500V~ (t=1s)
600V~ (t=1s)
690V~ (t=1s)
230-690V~ (t=3s)
with maintenance
without maintenance
DMX
-1600
3
3p-4p
630/800/1000/1250/1600
1000
12
690
105
105
105
88
88
50
50
50
42
42
25
YES
10000
5000
3000
15ms
30ms
S
S
S*
O
O
O
O
O
O