INSTALLATION MANUAL
INTBUSW
Wiegand door controller

1] GENERAL INFORMATION

Wiegand communications protocol
with multitechnologies
heads (proximity, RF, Mifare
Centralised or autonomous
operation modes.
2 relays:
- locking system,
- alarm.
Contacts: tag reading
authorization and opening/closing
door detection (alarms).
Supplied in a sealed box.
Central controller communication
by BUS RS485 (3 wires).
Connection of an exterior
and exit push button.
Operating voltage:
- 12 V AC/DC
- 24 V DC.
Consumption: 150 mA.
2] NOTES AND RECOMMENDATIONS
Wiring reminder
- the distance between a reader and the (INTBUSW)
door controller is 50m maximum.
- the distance between a central controller or panel
and the last (INTBUSW) door controller may be up
to 1000m maximum.
- take care not to pass your wires close to «High
voltage» cables (e.g.: 230 V AC).
- recommended cables > SYT1 shielded cable,
1 twisted pair 8/10ths (shielded cables), please
read the article below: « A EIA-485 Bus network
can connect in parallel several devices which
have a transmitter and a receiver. The maximum
length is 1220 meters between the controller
and the last reader. If the distance exceeds
10 meters then it is necessary to connect
the GND (0V) between each devices (then
the RS485 communication bus requires 3 core
cable, 2 plus the shield) to prevent, that
the voltage between the OV and the OV
and the GND, from damaging the devices.»
cdvi.com
2
cdvigroup.com
reader
®
, etc.)
®
Fitting
In order to optimise the mounting of the door
controller, it should be fi tted on a fl at surface.
Environment
The door controller absolutely must be installed in
a closed environment and protected from exterior
climatic conditions.
Installation recommendations
To protect the installation, remember to:
- install the varistor in parallel on the locking system
- install a 120 ohm resistor between A and B
- The readers must be installed one at a time
Recommended power supplies
- ARD12 or BS60.
WEEE
CE Certifi cation
IP52
-20°C to +70°C
power supply side.
on the last BUS RS485 door controller.
(can not program the readers at the same time).