GROUNDING INSTRUCTIONS
For correct operation of the meter, it is NECESSARY that the sensor and the
liquid are equipotential, so ALWAYS connect the sensor and converter to
ground:
Grounding with metallic pipe
o
Sensors with ground socket
on the connection box
Grounding with insulating pipe
o
INSULATING GASKET
METALLIC
RING
Grounding when there is a cathodic protection over the pipe
o
o
INSULATING GASKET
ISOIL
INSULATING
BUSH
METALLIC RING
Wafer sensors
If the sensor is mounted on a pipe made of an insulating material,
If the sensor has to be mounted on a
do one of the following:
pipe made of an insulating material
-
Install a metallic ring between the sensor flange and the
is necessary:
pipe counter flange,
-
or use a sensor with the additional grounding electrode.
If the sensor is mounted on a pipe with a cathode protection, do the
If the sensor must be install
following:
in the piping with a chatode
-
use insulating bushes to isolate the bolts,
protection, is necessary:
-
insert insulating gaskets on both sides of the rings to
ground the metallic rings and hence the liquid.
7
SENSOR FOR ELECTROMAGNETIC FLOW METER – MANUAL
Flanged sensors
- Install two metallic ring between
the sensor flanges and the counter
flanges of the pipe line or:
- Use a sensor with the additional
grounding electrode
- using insulating bushes to isolate
the bolts
- Grounding metallic rings should be
provided to ground the liquid using
insulating gasket between the rings
- IMPORTANT :
-
IMPORTANT :
The ripple of DC power source used
The ripple of DC power
for cathodic protection
source used for
shall be = 0
cathodic protection
must be 0.
ESENS_FULLBORE_05.doc